IM02602002E
www.eaton.com
Page
1-1
MP-3000
SECTION 1 - INTRODUCTION
1.0 General
The MP-3000 is an advanced microprocessor-based motor protection
relay that is easy to set up and use. It monitors, controls, and protects
motors against overload, thermal damage to rotor or stator, electrical
faults, and excessive starting, and many process equipment failures.
Advanced algorithms and thermal models give safe operation over a
wide range of conditions.
The MP-3000 protects 50 or 60 Hz three-phase motors of any size
or voltage level. It can protect induction or synchronous motors, with
or without RTDs. The relay is frequently installed in motor starters or
switchgear.
The MP-3000 Motor Protection Relay provides the following pro-
tection, alarm, and control functions. ANSI device numbers are in
parentheses.
Protection
Intel-I-Trip I2t Overload Protection (49/51)
Locked-rotor protection (49S/51)
Ultimate trip current (51)
Negative sequence current/phase unbalance and reverse
phase protection (46)
Instantaneous overcurrent trip (50)
Ground fault protection (50G)
RTD trip with accessory URTD module (49/38)
Underload trip power and current (37)
Starts per time limit (66)
Jam or stall trip (51R)
Zero-speed switch trip (14)
I2t Auto or manual reset (86)
Fail-safe or non-fail-safe trip modes
alarming
Ground fault
I2t Overload
Jam / Stall
Underload
Phase unbalance
RTD temperature with URTD module
Control
features
Transition control for reduced voltage starters
Incomplete sequence (process feedback) detection and trip
Permits user-set number of cold starts
Limits number of starts per time
User sets minimum time between starts
Antibackspin (time from stop to next start) delay
Current-based process load shedding and restoration
Long acceleration timing feature
Motor stop input for synchronous motor and condenser
applications
Remote trip input
Differential trip input
Emergency override clears blocks to motor restarting (if
enabled)
Program settings while motor runs, with controlled change
-
over (if enabled)
Disarmed mode for commissioning and checking in a
running process
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
•
1.1 Replacing the IQ 1000 II with the MP-3000
The MP-3000 Motor Protection Relay serves as a direct replacement
for the prior generation Westinghouse
®
or Cutler-Hammer IQ 1000 II.
The cutout and mounting are compatible. The relay terminal configu
-
ration and wiring connections are similar.
CaUTION
TERMINaL 6 (SEE fIGURE 6.3) WaS REMOTE COMMON IN ThE
IQ1000II. ThIS TERMINaL PROVIDED a CONNECTION TO NEU
-
TRaL If 120 VaC CONTROL POWER WaS USED, aND a 120 VaC
SOURCE If 240 VaC CONTROL POWER WaS USED. ThE IQ1000
II haD a faCTORy INSTaLLED jUMPER BETWEEN TERMINaL 6
aND TERMINaL 9 - ThE COMMON RETURN Of ThE DISCRETE
INPUT ChaNNELS.
Do not install this jumper on the mp-
3000.
ThE MP-3000 USES TERMINaL 6 fOR DISCRETE SOURCE
aND IT IS a CONNECTION TO 120 VaC IN BOTh CaSES Of 120
VaC aND 240 VaC CONTROL POWER USE. REfER TO SECTION
6,
installation anD Wiring
fOR PROPER WIRING Of ThE
DISCRETE INPUTS.
1.2 MP-3000 features and Enhancements
The MP-3000 Motor Protection Relay incorporates the field proven
motor thermal models and sequence component measurement
techniques that were pioneered in the IQ 1000 II relay thermal models.
The MP-3000 also adds several enhancements. Significant enhance
-
ments and features include:
1. Recognized to meet UL 1053 Standards for Ground Fault Protec
-
tion Devices.
2. Power supply operates continuously at 55% of nominal supply
voltage. It can ride through a voltage sag or loss for 30 cycles
without dropping out and taking the motor off line.
3. Optional Quick Release Drawout Case that makes removal and
replacement fast and easy.
4. New Armed/Disarmed feature for trip-free installation with Quick
Release Drawout Case.
5. User selectable trip or alarm only on relay internal failure detec
-
tion.
6. Real-time clock for date and time stamping of trips, alarms, and
events (Y2K compliant).
7. Expanded memory for extensive recording and logging of events,
trips, alarms, history, and motor starting current profiles.
8. Motor starting profile plot versus protection limits.
9. Easy-to-use faceplate and user interface. Settings and data are
organized into pages under six main modes. The modes are
Default (motor state), Monitor, View Setting, History, Logs, and
Program (change settings).
10.
intel-i-trip
Intelligent Overload Protection with adaptive trip char-
acteristics based on RTD readings and motor operating history.
11. RTD diagnostics and communications error checking for addi
-
tional security against operation from RTD failures.
12. Mechanical Process Load Shedding feature provides overload
indication to control upstream processes, averting unnecessary
motor overload shutdown or jam trips, and maintaining process
continuity.
Содержание MP-3000
Страница 1: ...IM02602002E www eaton com IM02602002E Rev E MP 3000 Motor Protection Relay ...
Страница 18: ...IM02602002E Page 4 www eaton com MP 3000 This Page Intentionally Left Blank ...
Страница 32: ...IM02602002E Page 4 20 www eaton com MP 3000 This Page Intentionally Left Blank ...
Страница 50: ...IM02602002E Page 6 www eaton com MP 3000 DIMENSIONS IN INCHES CM Figure 6 3 MP 3000 Case Depth Dimensions ...
Страница 53: ...IM02602002E www eaton com Page 6 MP 3000 Figure 6 6 MP 3000 Typical CT Circuit and Motor Control Wiring ...
Страница 54: ...IM02602002E Page 6 10 www eaton com MP 3000 Figure 6 7 Typical AC Supply and URTD Wiring ...
Страница 55: ...IM02602002E www eaton com Page 6 11 MP 3000 Figure 6 8 Alternatives for Discrete Input Wiring ...
Страница 60: ...IM02602002E Page 7 www eaton com MP 3000 This Page Intentionally Left Blank ...
Страница 71: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 1 Rotor Temperature Tracking ...
Страница 72: ...IM02602002E Page 9 www eaton com MP 3000 Figure 9 2 Motor Protection Curve ...
Страница 73: ...IM02602002E www eaton com Page 9 MP 3000 Figure 9 3 Underload Jam Protection Curve ...
Страница 74: ...IM02602002E Page 9 10 www eaton com MP 3000 Figure 9 4 Motor Protection Curve Example without RTDs ...
Страница 75: ...IM02602002E www eaton com Page 9 11 MP 3000 Figure 9 5 Motor Protection Curve Example with RTDs ...
Страница 76: ...IM02602002E Page 9 12 www eaton com MP 3000 Figure 9 6 Motor Start and Run Cycles ...
Страница 79: ...IM02602002E www eaton com Page 10 MP 3000 Figure 10 1 PONI Communications Module ...
Страница 90: ...IM02602002E Page 12 www eaton com MP 3000 This Page Intentionally Left Blank ...