Switching on Contactors DIL-
SWD-32-001, DIL-SWD-32-002
36
06/09 AWB2723-1613en
Table 3:
Power consumptions of the contactor coils with a
voltage of 24 V DC
Contactor
Pull-in power
Pick-up
current with
24 V DC
Sealing power
Holding
current with
24 V DC
[W]
[mA]
[W]
[mA]
DIL7 - DIL9
3
125
3
125
DIL12 - DIL15
4.5
188
4.5
188
DIL17 - DIL38
12
500
0.5
21
h
Caution!
The sum of the pull-in power of the simultaneously
tripping contactors and the sum of the holding power of
the tripped contactors for each SmartWire-Darwin
network must not exceed 72 W. If required, an additional
power feeder module (EU5C-SWD-PF1-1, EU5C-SWD-PF-
2) must be used (
chapter "Power Module EU5C-SWD-
h
The DIL modules draw their energy for the communication
electronics and for actuation of the LEDs and of the
auxiliary contacts from the SmartWire-Darwin network
supply. Please take into consideration the total power
consumption of your SmartWire-Darwin network and, if
necessary, plan for an additional feeder module EU5C-
SWD-PF2-1.
h
For data for the current requirement please refer to the
table in the appendix on page 105.