Technical data
123
06/09 AWB2723-1613en
Coupling, plug
SWD4-
8SFF2-5
SWD4-
8SF2-5
SWD4-8FRF-
10
General
Standards
IEC/EN 61131-2, EN 50178
Dimensions (W
x
H
x
D)
mm
48.5
x
34.5
x
10
15
x
36.5
x
17.5
35
x
90
x
35
Weight
g
4.5
5.5
42
Mounting position
any
any
any
Ambient mechanical conditions
Protection type (IEC/EN 60529)
IP20
IP20
IP20
Vibrations (IEC/EN 61131-2:2008)
constant amplitude 3.5 mm
Hz
5 … 8.4
5 … 8.4
5 … 8.4
constant acceleration 1 g
Hz
8.4 … 150
8.4 … 150
8.4 … 150
Mechanical shock resistance (IEC/EN
60068-2-27)
semi-sinusoidal 15 g/11 ms
Shocks
9
9
9
Electromagnetic compatibility (EMC)
Electrostatic discharge (IEC/EN 61131-2:2008)
Air discharge (Level 3)
kV
8
–
–
Contact discharge (Level 2)
kV
4
–
–
Ambient climatic conditions
Operating ambient temperature (IEC
60068-2)
°C
–25 … +55
–25 … +55
–25 … +55
Condensation
prevent with suitable
measures
Storage
°C
–40…70
–40…70
–40…70
Relative humidity, non-condensing (IEC/
EN 60068-2-30)
%
5 … 95
5 … 95
5 … 95
Connection options
SWD-In
Plug, 8-pole
Plug
connector
Plug, 8-pole
Number of insertion cycles
≥
200
1
≥
200
SWD-Out
Plug, 8-pole
Socket, 8-
pole
Push in
terminals
Number of insertion cycles
≥
200
≥
200
–
Current consumption (15 V SWD supply)
Содержание Moeller SmartWire-Darwin Series
Страница 8: ...4 06 09 AWB2723 1613en...
Страница 12: ......
Страница 36: ...32 06 09 AWB2723 1613en...
Страница 66: ...62 06 09 AWB2723 1613en...
Страница 108: ...104 06 09 AWB2723 1613en...
Страница 130: ...126 06 09 AWB2723 1613en...