Download this project to the CompactLogix controller. The software will be online
with the controller when the download is complete. The I/O LED on the controller
should be on solid, not flashing. This indicates that the controller is properly
polling the SmartWire-DT gateway, with no errors. If the I/O LED is flashing,
double click the 1769-L23E-QB1 Ethernet Port LocalENB and confirm that the
online Ethernet parameters on the Port Configuration tab are correct, i.e. that
they match the offline parameters. If not, change them and click the SET button.
In the Controller Tag data base, the following tags will have been created:
Input Tags: EIPSWD:I.Data(0) through EIPSWD:I.Data(10)
Output Tags: EIPSWD:O.Data(0) through EIPSWD:O.Data(7)
The first 2 input bytes contain status information from the SmartWire-DT
gateway. The next 9 input bytes are for the 9 SmartWire-DT devices connected
to the Ethernet SmartWire-DT gateway. In SWD-Assist, either online of offline,
click any of the SmartWire-DT devices and under that devices Device Information
tab will be displayed the meaning of each input and output bit for that device. If
you named your SmartWire-DT gateway EIPSWD in RSLogix 5000, the tags
created by RSLogix 5000 based on the Ethernet configuration will be as follows: