Publication Number AD05006002E
Page 16
Single click on the EU5C-SWD-EIP-MODTCP gateway. The Device Information
tab should look like the following:
Gateway:
STOP
Data Transfer:
Outputs switched off
SWD:
RUN
Device name:
EIPSWD
Description:
EtherNet/IP / Modbus TCP Gateway / SWD
EtherNet/IP parameters:
Assembly
instance Size
Inputs
101 11 Byte
Outputs
100
8 Byte
Configuration
102
0 Byte
The Input, Output and Configuration Assembly Instance numbers and the
number of bytes for each is displayed on this tab. This is the information needed
for the EtherNet/IP master to poll the EU5C-SWD-EIP-MODTCP Ethernet
gateway to control and monitor the connected SmartWire-DT devices.
Another piece of necessary information required by the Ethernet master is the IP
address of the gateway.
EU5C-SWD-EIP-MODTCP IP Address: 192.168.1.3
CompactLogix IP Address: 192.168.1.2
Both devices have a Subnet mask of: 255.255.255.0.
Take SWD-Assist offline. Start RSLogix 5000® by double clicking its icon on your
desktop. Create a project, selecting the CompactLogix L23E as the controller.
On the left portion of the project screen in RSLogix 5000, under: I/O
configuration/CompactLogix5323E-QB1 System/1769-L23E-QB1 Ethernet Port
LocalENB right click on Ethernet and select New Module. Then, under
Communications, select ETHERNET-MODULE Generic Ethernet Module. The
following window will open: