manualshive.com logo in svg
background image

Publication Number AD05006002E  

Page 16 

 

Single click on the EU5C-SWD-EIP-MODTCP gateway. The Device Information 
tab should look like the following: 
 

 

 
 
 
 

Gateway: 

STOP 

 

Data Transfer: 

Outputs switched off 

 

SWD: 

RUN 

 

 

Device name: 

EIPSWD  

Description: 

EtherNet/IP / Modbus TCP Gateway / SWD  

 

 
EtherNet/IP parameters:  

 Assembly 

instance Size 

Inputs 

101 11 Byte

Outputs 

100

8 Byte

Configuration

102

0 Byte

 

 
The Input, Output and Configuration Assembly Instance numbers and the 
number of bytes for each is displayed on this tab. This is the information needed 
for the EtherNet/IP master to poll the EU5C-SWD-EIP-MODTCP Ethernet 
gateway to control and monitor the connected SmartWire-DT devices. 
 
Another piece of necessary information required by the Ethernet master is the IP 
address of the gateway. 
 
EU5C-SWD-EIP-MODTCP IP Address: 192.168.1.3 
CompactLogix IP Address: 192.168.1.2 
 
Both devices have a Subnet mask of: 255.255.255.0. 
 
Take SWD-Assist offline. Start RSLogix 5000® by double clicking its icon on your 
desktop. Create a project, selecting the CompactLogix L23E as the controller.  
 
On the left portion of the project screen in RSLogix 5000, under: I/O 
configuration/CompactLogix5323E-QB1 System/1769-L23E-QB1 Ethernet Port 
LocalENB right click on Ethernet and select New Module. Then, under 
Communications, select ETHERNET-MODULE Generic Ethernet Module. The 
following window will open: 
 

Содержание Moeller DIL-SWD-32-002

Страница 1: ...onfigure a SmartWire DT system and how to set up an Ethernet master to control and monitor all devices on that SmartWire DT system A Rockwell CompactLogix controller will be used to demonstrate EtherN...

Страница 2: ...hernet gateway 3 DIL SWD 32 002 contactor modules 1 M22 SWD LED R red LED module 1 M22 SWD K22LED W start stop pushbutton with white LED module 1 M22 SWD K22LED G selector switch with green LED module...

Страница 3: ...ab drag and drop it onto the project screen over the PROFIBUS DP gateway It will drop onto the other gateway replacing it Then click the gateway s icon on the project screen Then click the Device Para...

Страница 4: ...nclosure on the project screen This is indicating that the flat cable must be converted to the round cable for connection to the M22 enclosure First we need to add an adapter that converts the flat ca...

Страница 5: ...oject and the Communication views Or under the View drop down menu select Communication View to toggle between the Project and Communication views This icon contains a gear and if you hold the cursor...

Страница 6: ...the SmartWire DT system Using the Auto Configuration Feature to Build and Configure a SmartWire DT System If the procedure above was used to build configure and download a SmartWire DT system you may...

Страница 7: ...part numbers shown earlier in this document 3 Add the following flat to round cable adapter between the M22 SWD K22LED G and the M22 I3 enclosure SWD4 8FRF 10 Note that when the software allows you to...

Страница 8: ...ges in the gateway This is what the Modbus TCP master reads and writes from to the gateway In SWD Assist in the offline mode the SmartWire DT gateway will display the total number of input and output...

Страница 9: ...nder each device s Device Information tab the actual Modbus Data Address for each bit will be displayed Note that the high byte of the first input and output data register is where the input and outpu...

Страница 10: ...portion of the screen above to modify the Ethernet parameters online Apply the changes and they will be saved in the gateway Gateway SWD and System settings may also be viewed or modified from this sc...

Страница 11: ...Input and Output data is shown above Double click the ELCSoft icon to open the ELC programming software ECISoft must have been previously installed then the ECISoft icon on the ELCSoft toolbar will o...

Страница 12: ...Publication Number AD05006002E Page 12 ECISoft will look like the following...

Страница 13: ...nline to configure the Ethernet master module Then click the M icon on the tool bar indicated by the arrow in the screen shot above and the software will find the ELC COENETM module Double click the m...

Страница 14: ...ws SW Device Modbus Data Address ELC PV data table DIL SWD 32 002 1 Input 0 8 0 15 D300 high byte Output 2048 8 D310 high byte DIL SWD 32 002 2 Input 0 0 0 7 D300 low byte Output 2048 0 D310 low byte...

Страница 15: ...l a SmartWire DT system with the EU5C SWD EIP MODTCP Ethernet gateway The SmartWire DT gateway is a slave on EtherNet IP and a master on the SmartWire DT network The data for each SmartWire DT device...

Страница 16: ...D EIP MODTCP Ethernet gateway to control and monitor the connected SmartWire DT devices Another piece of necessary information required by the Ethernet master is the IP address of the gateway EU5C SWD...

Страница 17: ...Name EIPSWD Comm Format Data Sint IP Address 192 168 1 3 Input Assembly Instance 101 Size 11 bytes 8 bit Output Assembly Instance 100 Size 8 bytes 8 bit Configuration Assembly Instance 102 Size 0 byte...

Страница 18: ...P MODTCP module Then double click the 1769 L23E QB1 Ethernet Port LocalENB also under Ethernet to open the EtherNet IP master port s Property Pages On the General Tab enter the IP address for the Comp...

Страница 19: ...change them and click the SET button In the Controller Tag data base the following tags will have been created Input Tags EIPSWD I Data 0 through EIPSWD I Data 10 Output Tags EIPSWD O Data 0 through E...

Страница 20: ...Publication Number AD05006002E Page 20 With this information the CompactLogix controller program can be written to control and monitor these SmartWire DT devices via EtherNet IP...

Страница 21: ...1 877 ETN CARE or 1 877 326 2273 All other supporting documentation is located on the Eaton web site at www eaton com plc or www eaton com smartwiredt SmartWire DT and SWD Assist are registered tradem...

Отзывы: