Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
48/55
Status description
Status to 0
Status to 1
Word (hex)
Bit
Mains 2 overload
no
yes
46
5
Mains 2 thermal overload
no
yes
46
6
Output on bypass
no
yes
46
7
Mains 2 frequency out of tolerance
no
yes
46
9
Mains 2 voltage out of tolerance
no
yes
46
A
Phase M2 out of tolerance
no
yes
46
B
Circuit breaker Q4S status
open
close
46
E
Internal fault
absent
present
47
0
Synchronization source
47
1 & 8
Mains 2 internal fault
absent
present
47
2
Charger general fault
no
yes
49
0
Battery charge
no
yes
49
1 & 3
Chopper fault
absent
present
4A
1
Rectifier short circuit
absent
present
4A
2
Inverter major fault
no
yes
4C
1
Inverter overload
no
yes
4C
2
Inverter thermal overload
no
yes
4C
3
Inverter limitation
no
yes
4C
4
UPS fuse fault
absent
present
4C
5
Over temperature
absent
present
4C
A
Short circuit
no
yes
4F
1
Output frequency out of range
no
yes
50
5
Electronic power supply fault
no
yes
50
6