6.6 Data for Eaton 5PX and Eaton 5P
6.6.1 Status table
Status description
Status to 0
Status to 1
Word (hex)
Bit
Load protected
no
yes
40
0
UPS coupled
no
yes
40
1
Unit general alarm
no
yes
40
2
UPS in backup
no
yes
40
4
Battery low warning
no
yes
40
5
Low battery
no
yes
40
6
Communication fault
absent
present
40
9
UPS overload
no
yes
40
A
Emergency stop
absent
present
40
B
Battery to be checked
no
yes
40
D
Device ventilation fault
no
yes
40
E
UPS Class
001 : off line / line interactive
011 : on line - unitary/parallel
100 : on line
– parallel with NS
101 : on line
– hot standby
redundancy
41
1 to 3
Battery present
absent
present
42
0
Mode buck
no
yes
44
0
Mode Boost
no
yes
44
1
Mains 1 voltage out of tolerance
no
yes
44
8
Mains 1 frequency out of tolerance
no
yes
44
B
Charger general fault
no
yes
49
0
Battery charge
no
yes
49
1 & 3
Short circuit
no
yes
4F
1