Modbus MS Card
– User Manual
34009048XT_EN/AD
Page
14/55
3.3 Configuration of the JBUS/MODBUS communication parameters
Use the cord supplied with the card.
Connect the card to a computer equipped with a Hyper terminal type emulator. The serial link must be set at 9600 baud, 8 bits,
no parity, 1 stop bit, and without flow control.
Check that UPS power is on.
Enter the
admin
password (not upgradable).
Connect the RS232 link to a
terminal
(Microsoft Hyper terminal)