9 Technical data
9.5 Interfaces
66
MICRO PANEL XV-152
12/2011 MN04802006Z-EN
www.eaton.com
Tab. 36 POW/AUX (power supply interface for SmartWire-DT)
1) If contactors and/or motor starters with a total power consumption > 3 A (DIN VDE 0641, Part 11 and IEC/EN 60898) or > 2 A
(UL 508 and CSA-22.2, No. 14) are connected, a power feeder module EU5C-SWD-PF1 or EU5C-SWD-PF2 has to be used.
9.5.2.2
SWD (SmartWire-DT interface)
Tab. 37 SWD (SmartWire-DT interface)
1) If SmartWire-DT slaves with a total power consumption > 0.7 A are connected, a power feeder module EU5C-SWD-PF2 has
to be used.
Repetition rate
1 s
Status indication
Yes (LEDs)
Property
XV-152
Property
XV-152
SmartWire-DT supply voltage U
VP
Rated operating voltage
(internally transformed supply voltage U
Pow
)
14.5 VDC ±3 % (14.0…15.0 VDC)
Current
Max. 0.7 A
1)
Short-circuit strength
Yes
Number of SmartWire-DT slaves on the
SmartWire-DT netwerk
Max. 99
Address setting of the SmartWire-DT slaves
Automatic
Baud rate
125 Kbit/s
250 Kbit/s
Содержание Micro Panel XV-102
Страница 1: ...Operating Instructions 12 2011 MN04802006Z EN XV 152 MICRO PANEL...
Страница 18: ...3 Safety regulations 3 4 Device related hazards 18 MICRO PANEL XV 152 12 2011 MN04802006Z EN www eaton com...
Страница 52: ...6 Operation 6 4 Inserting and removing an SD card 52 MICRO PANEL XV 152 12 2011 MN04802006Z EN www eaton com...
Страница 70: ...9 Technical data 9 9 Ambient conditions 70 MICRO PANEL XV 152 12 2011 MN04802006Z EN www eaton com...