MaGnuM PRoDuct GuiDe
CA013002EN—April 2017 www.eaton.com
59
Technical data and endurance information for installation
Technical data for usual service conditions (0°C to 40°C)
•
Ambient temperatures & thermal derating tables
Magnum breakers are tested and fully rated for use in
ambient temperatures from 0°C to 40°C . Thermal de-rating
tables are provided for different Magnum breakers operating in
switchboards at various ambient temperatures above 40°C .
The switchboard’s ambient should be estimated using an
industry accepted calculation method .
Magnum DS and SB ANSI temperature derating tables
Table 19 . Calculated de-rated capacity ANSI standard
Frame
actual ambient temperature (°c)
40
45
50
55
60
70
800
800
800
800
794
738
612
1600
1600
1600
1600
1600
1592
1321
2000
2000
2000
1995
1869
1735
1439
2500
2500
2395
2259
2116
1965
1630
3000
3000
2845
2684
2514
2334
1936
3200
3200
3098
2922
2737
2541
2108
4000
4000
4000
3815
3574
3318
2752
5000
5000
5000
4716
4417
4101
3402
Table 20 . Calculated de-rated capacity ANSI narrow
Frame
actual ambient temperature (°c)
40
45
50
55
60
70
800
800
800
800
800
800
800
1200
1200
1200
1200
1200
1200
1101
1600
1600
1600
1526
1429
1327
1101
2000
2000
1916
1807
1693
1572
1304
Table 21 . Calculated de-rated capacity ANSI
MDSL Magnum
Frame
actual ambient temperature (°c)
40
45
50
55
60
70
800
800
800
800
800
800
763
1600
1600
1600
1600
1521
1413
1172
2000
2000
2000
1976
1851
1718
1425
Shaded means no loss in derating
Magnum IEC temperature derating tables
Table 22 . Calculated de-rated capacity for
IEC standard Magnum
Frame
actual ambient temperature (°c)
40
45
50
55
60
70
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1250
1250
1600
1600
1600
1600
1600
1600
1600
2000
2000
2000
2000
2000
2000
2000
2500
2500
2500
2500
2500
2500
2482
3200
3200
3109
2992
2871
2746
2482
4000SW
4000
4000
4000
4000
4000
3615
4000DW
4000
4000
4000
4000
4000
4000
5000
5000
5000
5000
5000
5000
5000
6300
6300
6300
6260
6008
5747
5193
Table 23 . Calculated de-rated capacity for
IEC narrow Magnum
Frame
actual ambient temperature (°c)
40
45
50
55
60
70
800
800
800
800
800
800
800
1000
1000
1000
1000
1000
1000
1000
1250
1250
1250
1250
1250
1100
1000
1600
1600
1600
1600
1600
1500
1350
2000
2000
2000
2000
2000
1800
1650
4000 NDW
4000
4000
4000
4000
3928
3549
Shaded means no loss in derating