MaGnuM PRoDuct GuiDe
CA013002EN—April 2017 www.eaton.com
54
Accessory devices and connections
•
Auxiliary switch
An auxiliary switch is an optional device providing remote
electrical indication if the circuit breaker is open or closed .
Up to three auxiliary switches can be mounted in one breaker .
Each switch has two normally open (“A”) and two normally
closed (“B”) contacts for a total of 12 available contacts .
Table 17 . Auxiliary switch, overcurrent trip switch, and
cell switch contact ratings
control voltages
contact rating inductive load (amperes)
250 Vac
10
125 Vdc
0.5
250 Vdc
0.25
Auxiliary switch (2A/2B)
Internal electrical accessories
Other electrical accessories are mounted inside the circuit
breaker . They can be factory or site installed . There are three
different internally mounted accessories:
1 . Overcurrent Trip Switch (Bell Alarm)
2 . Mechanical Trip Flag Pop-out Indicator
3 . Motor Operator
•
Overcurrent trip switch (bell alarm)
An overcurrent trip switch (bell alarm) is an optional device .
It provides an electrical indication when a circuit breaker trips
as a result of the trip unit reacting to an overcurrent condition .
Opening as a result of a circuit breaker’s manual open button,
shunt trip, or undervoltage release does not cause the
overcurrent trip switch to operate .
The status of the contacts changes when the trip indicator
pops out . This permits the switch to be used as an alarm or
in conjunction with a spring release to block a subsequent
remote electrical closing signal . Refer to Section 3 for
available options .
•
Mechanical trip flag pop-out indicator
The mechanical trip flag pop-out indicator is an overcurrent
indication feature that can be supplied as an option on
Magnum breakers with integral trip units . This device is located
just above the trip unit on the breaker’s front faceplate . In
the event the trip unit trips the breaker on an overcurrent
condition, the red trip flag releases and pops out to give local
visual indication . This trip indication is in addition to any LED
trip indication next to the protection feature .
The red flag can be reset by manually pushing it back in .
The breaker can be reclosed, even if the flag is not reset . An
optional Overcurrent Trip Switch (OTS) is available should an
electrical lockout be required on an overcurrent trip condition .
If the trip unit trips the breaker on an overcurrent condition:
•
Red mechanical trip flag indicator pops out
•
OTS contacts change state
The OTS Switch is reset by manually pushing in the red trip
flag . When the trip flag is reset, the OTS switch contacts
return to their normal state .
Mechanical trip
indicator
Mechanical trip indicator with associated overcurrent trip switch
•
Motor operator
A motor operator is an electric motor assembly internally
mounted in the circuit breaker . It charges the closing springs
electrically for remote or local operation . It can be factory or
site installed . A UL Listed motor operator kit is available to
make the conversion from a manually operated breaker to an
electrically operated breaker .
Table 18 . Motor operator ratings
control
voltages
operational
voltage
range
85–110%
Running
current
(a. avg.)
typical
inrush
current
Power
consump-
tion (W or
Va)
Maximum
charging
time
(seconds)
24 Vdc
20–26
12
300% of
running
300
5
48 Vdc
41–53
5
500% of
running
250
5
60 Vdc
51–66
3
600% of
running
250
5
110–125 Vdc 94–138
2
600% of
running
250
5
220–250 Vdc 187–225
1
600% of
running
250
5
110–127 Vac 94–140
2
600% of
running
250
5
208–277 Vac 177–305
1
600% of
running
250
5
AC voltages are 50/60 Hz .
1
1