MaGnuM PRoDuct GuiDe
CA013002EN—April 2017 www.eaton.com
46
Magnum trip units and communication devices
Digitrip trip units – Comprehensive features
Table 12 . Digitrip trip units for Magnum DS and SB ANSI/UL rated power circuit breaker
trip unit type
Digitrip 520
Digitrip 520M
Digitrip 520Mc
Digitrip 1150+
Ampere range
200–5000A
200–5000A
200–5000A
200–5000A
Interruption rating
at 480V
42–200 kA
42–200 kA
42–200 kA
42–200 kA
rms sensing
Yes
Yes
Yes
Yes
Protection and coordination
Protection
Ordering options
LI, LSI, LSIG, LSIA
LSI, LSIG
LSI, LSIG
LSI, LSIG, LSIA
Fixed rating plug (I
n
)
Yes
Yes
Yes
Yes
Overtemperature trip
Yes
Yes
Yes
Yes
Long delay
protection
(L)
Long delay pickup
0.4–1.0 x (I
n
)
0.4–1.0 x (I
n
)
0.4–1.0 x (I
n
)
0.4–1.0 x (I
n
)
Long delay time I
2
t at 6 x I
r
2–24 sec
2–24 sec
2–24 sec
2–24 sec
Long delay time I
4
t
No
No
No
1–5 sec
IEEE curves
No
No
No
Yes
Long delay thermal memory
Yes
Yes
Yes
Yes
High load alarm
No
No
No
0.5–1.0 x (I
r
)
Short delay
protection
(S)
Short delay pickup
200–1000% x (I
r
) & M1
200–1000% x (I
r
) & M1
200–1000% x (I
r
) & M1
200–1000% x (I
r
) & M1
Short delay time I
2
t at 8 x I
r
100–500 ms
100–500 ms
100–500 ms
100–500 ms
Short delay time flat
100–500 ms
100–500 ms
100–500 ms
100–500 ms
Short delay time ZSI
Yes
Yes
Yes
Yes
Instantaneous
protection
(I)
Instantaneous pickup
200–1000% x (I
n
) & M1
200–1000% x (I
n
) & M1
200–1000% x (I
n
) & M1
200–1000% x (I
n
) & M1
Making current release
Yes
Yes
Yes
Yes
Off position
Yes
Yes
Yes
Yes
Ground fault
protection
(G)
Ground fault alarm
No
Yes
Yes
Yes
Ground fault pickup
25–100% x (I
n
)
25–100% x (I
n
)
25–100% x (I
n
)
24–100% x (I
n
)
Ground fault delay I
2
t at 0.625 x I
n
100–500 ms
100–500 ms
100–500 ms
100–500 ms
Disable ground fault
protection
No
No
No
No
Neutral protection (N)
Model LSI only
Model LSI only
Model LSI only
Model LSI only
System diagnostics
Cause of trip LEDs
Yes
Yes
Yes
Yes
Magnitude of trip
information
No
Yes
Yes
Yes
Remote signal
contacts
No
Yes
Yes
Yes
Programmable
contacts
No
No
No
Yes
Electronic operations
counter
No
No
No
Yes
Over and undervoltage alarm or trip, over and underfrequency alarm or trip, voltage unbalance a larm or trip, reverse power trip and phase rotation
alarm are included .
1200A maximum ground fault setting per UL/NEC .
I
n
= Rating plug and sensor rating .
I
r
= Long delay pickup setting .
1
2
2