Form 6 recloser control KME6-1875-1, KME6-1875-2, and KME6-1875-3  

fiber optic converter kits installation instructions

7

InstallatIon InstructIons

   MN280079EN   May 2017

TB1

1

2

3

5

7

9

11

13

15 17

19

4

6

8

10

12

14

16

18

CI1 CI2 CI3 SS1

CO1

CO2 CO3 CO4

CI4

CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4

TB3

1

3

5

7

9

11

13

15

17

19

21

CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5

CO6

TB4

2

4

6

8

10

12

14

16

18

20

CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6

1

3

5

7

9

11

13

CO7 CO8 CO9 CO10 CO11 CO12

2

4

6

8

10

12

CO7 CO8 CO9 CO10 CO11 CO12

J1 -RS-232

J2 -IRIG-B

TTL IRIG-B

J3 -RS-485

2-Wire RS-485

RECLOSER INTERFACE CONNECTIONS

A

1

D

3

F

5

7

2

B

4

C

6

E

TB6

RS-232 DTE

TB2

1

2

3

4

5

6

7

8

9

10

11

12

13

14

15 16

17

18

19

20

I

(1-2)

I

(3-4)

I

(5-6)

V

(1-2)

V

(3-4)

V

(5-6)

V

1

I

(SEF)

FUSE

(10 AMP)

FUSE

(10 AMP)

TB5

+
1

-
5

2

-

4

+

INPUT POWER

AUXILIARY POWER

28 VDC

9-Pin Cable Connected
to RS-232 Port

OPTION 2*

Fiber Optic Power Cable

Connected to Terminal Block TB5

Black Wire Connected to TB5-5

Red Wire Connected to TB5-4

Fiber Optic Converter

Assembly

Grounding Stud

Ground to Earth with

customer-supplied

#6 grounding lug.

6 Foot Cable Length

6 Foot Cable Length

*OPTION 1 Connect fiber optic power cable to customer-supplied 24 Vdc
 (non-polarized) power source.

Mode Switch Set to the OFF Position

DTE/DCE Switch Set to the DCE Position

Figure 5 .  KME6-1875-3 fiber optic converter connected to the Form 6 rack mount recloser control

RS-232 Cable

Fiber Optic 

Power Cable

Grounding 

Stud

Figure 6 .  KME6-1875-3 fiber optic converter assembly 

parts identification

GND

STUD

1.77

0.25

4 PL.

2.12

Figure 7 .  KME6-1875-3 fiber optic converter mounting 
dimen-sions (inches) .

Содержание KME6-1875-1

Страница 1: ...m 6 recloser control KME6 1875 1 KME6 1875 2 and KME6 1875 3 fiber optic converter kits installation instructions COOPER POWER SERIES Reclosers MN280079EN Effective May 2017 Supersedes March 2003 S280 70 6 ...

Страница 2: ...RPOSE OR MERCHANTABILITY OTHER THAN THOSE SPECIFICALLY SET OUT IN ANY EXISTING CONTRACT BETWEEN THE PARTIES ANY SUCH CONTRACT STATES THE ENTIRE OBLIGATION OF EATON THE CONTENTS OF THIS DOCUMENT SHALL NOT BECOME PART OF OR MODIFY ANY CONTRACT BETWEEN THE PARTIES In no event will Eaton be responsible to the purchaser or user in contract in tort including negligence strict liability or other wise for...

Страница 3: ... iii Product information 1 Introduction 1 ANSI standards 1 Quality standards 1 Acceptance and initial inspection 1 Handling and storage 1 Description 1 Installation 1 KME6 1875 1 fiber optic converter kit for form 6 pole mount control 1 KME6 1875 2 fiber optic converter kit for form 6 yard mount control 4 KME6 1875 3 fiber optic converter kit for form 6 rack mount control 6 ...

Страница 4: ...ltage lines and equipment and support our Safety For Life mission Safety information DANGER Hazardous voltage Contact with hazardous voltage will cause death or severe personal injury Follow all locally approved safety procedures when working around high and low voltage lines and equipment G103 3 WARNING Before installing operating maintaining or testing this equipment carefully read and understan...

Страница 5: ... file a claim with the carrier immediately Handling and storage Be careful during handling and storage of the kit to minimize the possibility of damage If the kit is to be stored for any length of time prior to installation provide a clean dry storage area Description The fiber optic converter accessory provides a permanent link for two way real time serial communications with a remote terminal un...

Страница 6: ... switch is in the OFF position Note N The mode switch enables the repeater function in the REP position and disables it in the OFF position CAUTION Equipment damage Always wear a grounding wrist strap to control static electricity before handling circuit boards Failure to use this strap may result in circuit board damage T253 1 5 Mount the fiber optic converter on the mounting stud inside the back...

Страница 7: ... Service Information MN280077EN Form 6 Microprocessor Based Pole Mount Recloser Control Installation and Operation Instructions for the procedure Return the Control to Service Table 1 KME6 1875 1 form 6 pole mount recloser control fiber optic converter kit parts Item Description Quantity 1 Fiber optic converter assembly 1 2 Nut hex machine screw 10 32 KEPS stainless steel 1 TB1 1 2 3 5 7 9 11 13 1...

Страница 8: ...de switch is in the OFF position Note N The mode switch enables the repeater function in the REP position and disables it in the OFF position CAUTION Control damage De energize both ac and dc power prior to removing or installing any internal connections or circuit boards in the control Failure to comply can result in damage to the control T241 1 CAUTION Equipment damage Always wear a grounding wr...

Страница 9: ...mply can result in misoperation unintended operation equipment damage and personal injury G119 2 10 Return the Form 6 yard mount recloser control to service Refer to Service Information MN280076EN Form 6 Microprocessor Based Yard Mount Recloser Control Installation and Operation Instructions for the procedure Return the Control to Service TB1 1 2 3 5 7 9 11 13 15 17 19 4 6 8 10 12 14 16 18 CI1 CI2...

Страница 10: ...andling circuit boards Failure to use this strap may result in circuit board damage T253 1 5 Connect the loose end of the fiber optic power cable Choose one of these two options OPTION 1 Connect to customer supplied 24 Vdc non polarized power source or OPTION 2 Connect to Terminal Block TB5 A Connect the black wire to TB5 5 B Connect the red wire to TB5 4 Note N The RS 232 and power cables are six...

Страница 11: ...I 3 4 I 5 6 V 1 2 V 3 4 V 5 6 V1 I SEF FUSE 10 AMP FUSE 10 AMP TB5 1 5 2 4 INPUT POWER AUXILIARY POWER 28 VDC 9 Pin Cable Connected to RS 232 Port OPTION 2 Fiber Optic Power Cable Connected to Terminal Block TB5 Black Wire Connected to TB5 5 Red Wire Connected to TB5 4 Fiber Optic Converter Assembly Grounding Stud Ground to Earth with customer supplied 6 grounding lug 6 Foot Cable Length 6 Foot Ca...

Страница 12: ...ates Eaton com cooperpowerseries 2017 Eaton All Rights Reserved Printed in USA Publication No MN280079EN KA2048 610 Rev 01 May 2017 Eaton is a registered trademark All trademarks are property of their respective owners For Eaton s Cooper Power series product information call 1 877 277 4636 or visit www eaton com cooperpowerseries SAFETY FOR LIFE ...

Отзывы: