Form 6 recloser control KME6-1875-1, KME6-1875-2, and KME6-1875-3
fiber optic converter kits installation instructions
5
InstallatIon InstructIons
MN280079EN May 2017
CAuTION
Equipment misoperation . Do not connect this control
to an energized recloser until all control settings have
been properly programmed and verified . Refer to the
programming information for this control . Failure to
comply can result in control and recloser misoperation,
equipment damage, and personal injury .
G110 .3
9. Verify the RS-232 and RS-485 Communication Ports are
set for the intended protocol:
●
●
Modbus
●
●
DNP3 Protocol, Level 2
●
●
2179
The RS-232 and RS-485 data ports can be specified
with DNP3, 2179, or Modbus protocol. The protocol is
user-configured to either the RS-232 or RS-485 serial
ports via the ProView
TM
interface software.
Refer to the
Communications Workbench
TM
section of
Service Information S280-70-4 Form 6 Microprocessor-
Based Recloser Control Programming Guide
for
additional information.
CAuTION
Equipment misoperation . Do not energize this
equipment until all control settings have been properly
programmed and verified . Refer to the electronic control
installation manual for programming procedures . Failure
to comply can result in misoperation (unintended
operation), equipment damage, and personal injury .
G119 .2
10. Return the Form 6 yard mount recloser control
to service.
Refer to
Service Information MN280076EN Form 6
Microprocessor-Based Yard Mount Recloser Control
Installation and Operation Instructions
for the procedure
Return the Control to Service
.
TB1
1
2
3
5
7
9
11
13
15 17
19
4
6
8
10
12
14
16
18
CI1 CI2 CI3 SS1
CO1
CO2 CO3 CO4
CI4
CI1 CI2 CI3 SS1 CO1 CO2 CO3 CO4
TB3
1
3
5
7
9
11
13
15
17
19
21
CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5
CO6
TB4
2
4
6
8
10
12
14
16
18
20
CI4 CI5 CI6 CI7 CI8 CI9 CI10 CI11 CO5 CO6
1
3
5
7
9
11
13
CO7 CO8 CO9 CO10 CO11 CO12
2
4
6
8
10
12
CO7 CO8 CO9 CO10 CO11 CO12
J1 -RS-232
J2 -IRIG-B
TTL IRIG-B
J3 -RS-485
2-Wire RS-485
RECLOSER INTERFACE CONNECTIONS
A
1
D
3
F
5
7
2
B
4
C
6
E
TB6
RS-232 DTE
TB2
•
1
2
•
3
4
•
5
6
•
7
8
•
9
10
•
11
12
•
13
14
•
15 16
•
17
18
•
19
20
I
(1-2)
I
(3-4)
I
(5-6)
V
(1-2)
V
(3-4)
V
(5-6)
V
1
I
(SEF)
FUSE
(10 AMP)
FUSE
(10 AMP)
TB5
+
1
-
5
2
-
4
+
INPUT POWER
AUXILIARY POWER
28 VDC
#10 Terminal of Wire
Assembly Lead on
Mounting Stud
9-Pin Cable Connected
to RS-232 Port
Fiber Optic Power Cable
Connected to Terminal Block TB5
Black Wire Connected to TB5-5
Red Wire Connected to TB5-4
Fiber Optic Converter
Assembly
Mode Switch Set to
the OFF Position
DTE/DCE Switch Set
to the DCE Position
Figure 4 . KME6-1875-2 fiber optic converter installed in the Form 6 yard mount recloser control cabinet