 Jockey Pump Controllers

START PRESSURE

The pressure is set in PSI format. 

(To set in BAR format, refer to the JOCKEY Touch™ Operation Manual.)

Using the number buttons, enter the start pressure.

Pressing the 

Arrow

 button will delete the pressure values one character at a time. 

Once the pressure is programmed, press the 

Next

 button.

Pressing the 

Cancel 

button will return the display to the Panel Setup 1/2 screen.

All Quick Setup values must be re-entered. 

STOP PRESSURE

The pressure is set in PSI format. 

(To set in BAR format, refer to the JOCKEY Touch™ Operation Manual.)

Using the number buttons, enter the stop pressure.

Pressing the 

Arrow

 button will delete the pressure values one character at a time. 

Once the pressure is programmed, press the 

Next

 button.

Pressing the 

Cancel 

button will return the display to the Panel Setup 1/2 screen.

All Quick Setup values must be re-entered. 

MINIMUM RUN TIMER

The minimum run time can be set up to 999 seconds.

The timer can be disabled by pressing the               button.       

To re-enable the timer, press the 

Arrow

 button.

(The timer values are erased and must be re-entered).

Using the number buttons, enter the minimum run time.

Pressing the 

Arrow

 button will delete the timer values one character at a time.  

Once the minimum run time is programmed, press the 

Next

 button.

Pressing the 

Cancel 

button will return the display to the Panel Setup 1/2 screen.

All Quick Setup values must be re-entered. 

SETUP COMPLETE

Once all the functions have been set, press the OK button.

The display will return to the Main Display Screen.

Pressing the 

Cancel 

button will return the display to the Panel Setup 1/2 screen.

All Quick Setup values must be re-entered.

SET DATE

The date is set in MM/DD/YY format.

Using the number buttons, enter the current date.

Pressing the 

Arrow

 button will delete values one character at a time. 

Once the date is programmed, press the 

Next 

button.

This will advance the screen to the Quick Setup screen for setting the Start Pressure.

Pressing the 

Cancel 

button will return the display to the Panel Setup 1/2 screen.

All Quick Setup values must be re-entered. 