background image

i-on40 

Installation 

 

 

Page 11 

 

Figure 20 Keypad Connection 

Termination 

The i-on40 data bus uses the RS485 interface. 
Because of this the ends of the line in some 
configurations may be terminated to improve 
performance in electrically noisy environments or 
where there are long cable runs. Both control 
panel and keypads have a termination link on their 
PCBs (see 10 in Fig 3 for the control unit and 5 in 
Fig 8, 1b in Fig 12 and 6b in Fig 14 for the 
keypads). Fitting a jumper to the pins adds a 
termination to the cable. 

In a daisy chain configuration terminate each end 
of the chain (see Fig 19 ). 

In a star configuration: 

 

If there are only two keypads then this is the 
same as a daisy chain configuration. If 
required terminate at each keypad. 

 

If there are more than two keypads AND two 
cables are long while the remaining keypad 
cables are short (less than 10m) then it is 
possible to terminate at the two keypads with 
long cables. 

 

If there are more than two keypads BUT each 
keypad cable is more than 10m then 

DO NOT

 

terminate. 

Keypad Addressing 

Each keypad connected to an control unit must 
have a unique address. See Figures 8, 12 or 14 
for the position of the addressing jumpers. 

 

Figure 21 Keypad Addressing Jumpers 

To add a wired keypad to the bus of an existing i-
on40 installation, first remove all power from the 
control unit, both mains and battery. Make sure 
the address link on the new keypad is not fitted in 
the same position as any of the address links on 
keypads already connected to the control unit. 
Connect the new keypad and then apply power to 
the system. 

Re-using a V2.0 Keypad From an i-onEX 

If you wish to use a keypad that has previously 
been working on an i-onEX system, then you must 
first default the keypad address. 

Eaton’s Security 

Business recommends that you do this by deleting 
the keypad from the i-onEX system using the 
Installer Menu. However, if this is not possible 
then you must default the keypad address 
manually as follows: 

1.  Remove the power and data connections from 

the keypad to the system bus. 

2   Open the keypad and make sure that the 

keypad tamper switch is open. (It must stay 
open until step 9.) 

3.  Apply 12Vdc power to the 0V and 12V 

terminals on the keypad connector. DO NOT 
use the i-on40 bus for this. 
The navigation key LEDs flash rapidly. 

4.  Hold down keys D and 

 at the same time. 

After a few seconds you should hear a 
confirmation tone and the navigation LEDs 
start flashing about once per second. 

5.  Release the D and 

 keys. 

6.  Remove the 12V dc power from the keypad. 
7.  Select an address for the keypad by placing a 

jumper on the appropriate address pins (see 
Figure 21). 

8.  Connect the new keypad (see Figure 20). 
9.  Close the keypad and ensure that the tamper 

switch is closed. 

Backlight Control I-KP01 

You can control the appearance of the keypad 
backlights and set/unset LEDs by fitting links over 
the appropriate jumpers on the keypad PCB (see 
Figure 8 on page 6 for the position of the 
jumpers). 

The jumpers have the following functions: 

 

The set/unset LEDs 
are disabled. 

 

The set/unset LEDs 
shows the setting 
status of the system. 
(Full set is the left 
hand LED.) 
See Note on next 
page. 

 

The key backlights are 
disabled. They will 

4
3
2

4
3
2

1

2

4

3

4
3
2

4
3
2

ON

BRIGHT

BL

ABCD-ON

ON

BRIGHT

BL

ON

BRIGHT

BL

ABCD-ON

ON

BRIGHT

BL

ABCD-ON

ON

BRIGHT

BL

ON

BRIGHT

BL

ABCD-ON

ON

BRIGHT

BACKLIGHT

BACKLIGHT

BACKLIGHT

ABCD-ON

ON

BRIGHT

ON

BRIGHT

ABCD-ON

Содержание i-on40

Страница 1: ...i on40 Security System Installation Guide Issue 7...

Страница 2: ...but will not damage the equipment Caution Describes actions that will physically damage the equipment and prevent its proper function WARNING Describes actions that are hazardous to health or cause in...

Страница 3: ...on 15 Step 4 Connect Wired Zones 15 Four Wire Closed Circuit Connections 15 Two Wire Closed Circuit Connections 15 Fully Supervised Loop Connections 15 Connecting Wired Zones on KEY KPZ01 only 16 Step...

Страница 4: ...i on40 Page iv This page is intentionally blank...

Страница 5: ...odules are i dig02 ATS2 A switched telephone network PSTN module that allows the control unit to report alarm information using standard protocols such as Fast Format SIA and Contact ID and can also s...

Страница 6: ...lease see the i on Web Server Setup Guide for more instructions Note that Eaton s Security Business recommends using Internet Explorer Other browsers may not be fully compatible with the web browser i...

Страница 7: ...persecurity co uk for more information about the factors affection radio signal strength Siting the Control Unit Do site the unit Upright battery at the bottom Within a protected zone As high as possi...

Страница 8: ...Connector pins for Lid Tamper 5 Printed circuit board PCB 6 Cable entry holes for detector and keypad wiring 7 Transformer 8 Mains connector block Note yellow power rating label fitted next to the con...

Страница 9: ...y not used in UK Figure 4 Control Unit Main Connectors i KP01 Controls and Displays 1 LCD display 2 x 20 characters 2 Programming keys 3 Navigation keys 4 Alert LEDs 5 Setting and unsetting keys 6 Pan...

Страница 10: ...losed and open 6 Hold Up Alarm HUA keys 7 Number text keys Figure 9 KEY K01 KP01 KPZ01 Controls and Displays Opening the KEY K01 KP01 KPZ01 To open the unit unclip the caps covering the screws on the...

Страница 11: ...onnector for control unit bus 6 Jumpers for 6a Addressing not used in i onEX control units 6b LED functions and RS485 bus termination Figure 13 KEY KP01 Keypad PCB 1 Tamper switch 2 Sounder 3 Connecto...

Страница 12: ...an i on40 control unit two i kp01 keypads and 15 wired PIRs the system takes the following total quiescent current Device Current Control unit PCB 130mA 15 x PIRs at 15mA each 225mA i sd02 communicato...

Страница 13: ...ck Tamper Fit and connect the combined lid back tamper provided Ensure that the switch is oriented as shown in Figure 16 Figure 16 Lid Back Tamper Item 2 in Figure 3 shows the connector for the lid ba...

Страница 14: ...if the installation site has equipment that produces high levels of R F Radio Frequencies for example welding equipment If screened cable is required you should keep to the following guidelines 1 Avoi...

Страница 15: ...m Re using a V2 0 Keypad From an i onEX If you wish to use a keypad that has previously been working on an i onEX system then you must first default the keypad address Eaton s Security Business recomm...

Страница 16: ...ypad s local programming mode Entering Local Programming Mode 1 Apply 12Vdc to the keypad 2 Enter Installer Menu on the control unit if the keypad is connected to a system 3 Open the keypad tamper 4 P...

Страница 17: ...r KEY EP used by the KEY KPZ01 1 LED window 2 Retaining Screw 3 Removable Fixing Plate 4 Permanently attached cable Figure 22 External Prox Reader KEY EP Siting the External Prox Reader Do site the Ex...

Страница 18: ...igure 25 shows the wiring connections at the keypad Figure 25 Connecting the External Prox Reader Tone Volume All Keypads To alter the volume of non alarm tones from the keypad adjust the keypad sound...

Страница 19: ...tem Options Wire Zone Type Panel Zones option and select 2 wire CC If required you can use one pair of zone terminals as a common tamper provided you program that zone with the type Tamper from the In...

Страница 20: ...d 3 Zone 1 35 35 Alarm Keypad 3 Zone 2 36 35 Tamper Keypad 4 Zone 1 33 33 Alarm Keypad 4 Zone 2 34 33 Tamper To select the wiring type for the keypad zones use Installer Menu System Options Wired Zone...

Страница 21: ...an example of a general method of using the outputs to connect a wired sounder It is possible to program the TR terminal on the control unit see item 8 in Figure 4 as either CC or FSL Use Installer Me...

Страница 22: ...ector The communicator must provide 12Vdc to indicate a line fault for example if the Line Fault output at the communicator uses a relay connect the common terminal of the relay to 12Vdc and the norma...

Страница 23: ...oad the Profile Or Press to start with a blank system Note The Profile may not be EN50131 compliant The factory default is EN50131 compliant The control unit loads your choice of profile and then show...

Страница 24: ...of the Installer Menu 5 Assemble and close the control unit a Hook the lid of the control unit into the bottom of the case b Close the lid and then tighten the two fixing screws NOTE It is possible fo...

Страница 25: ...other sub options Leaving the Installer Menu If you wish to leave the Installer Menu at any time 1 Press until the display shows the words Leave installer mode 2 Press to leave Installer menu Press if...

Страница 26: ...Installer Menu and then leave it again The navigation key LEDs should now glow green Note The log is protected and cannot be erased by the Installer Restoring Factory Defaults If you wish to restore a...

Страница 27: ...Way Set Instant Duress Enable User reset Zone alarms 7 Zone tampers System tampers Confirmation UK Confirmation Mode Basic DD243 BS8243 Confirmation time 8 After entry 8 Entry keypad lock 8 Sounder o...

Страница 28: ...Appears only if System Options Confirmation Mode is BS8243 10 Appears only when Masking is ON 11 Appears only in EUR version 12 Appears in this position only in part setting systems 13 Appears only wh...

Страница 29: ...ntly clean the lenses of any PIRs with a clean soft dry cloth Do not use water solvents or any proprietary cleaning materials Walk test all detectors Test any external sounders and strobes Replacing o...

Страница 30: ...ocking Blocked for 90s after four incorrect codes or prox tags in series Blocked for a further 90s after each additional incorrect code or prox tag until next correct code or prox tag entered Proximit...

Страница 31: ...to EN50130 4 Emissions Conforms to EN61000 6 3 Outputs O P 1 2 Voltage free single pole relay contacts rated 24VDC 1A O P 3 4 Open collector transistor 12VDC when inactive 0V when active 500mA max Plu...

Страница 32: ...el top button is disabled 706rEUR 00 Two button HUD tilt switch transmitter 710rEUR 00 Two button HUD 726rEUR 50 Long range hand held HUD 726rEUR 60 Short range hand held HUD Detectors 713rEUR 00 Pet...

Страница 33: ...N Communication ARC only i gsm02 GSM communications module i sd02 PSTN Communication module with speech dialling Accessories 703rEUR 00 4 channel 2 zone transmitter 762rEUR 00 Two Channel Receiver 768...

Страница 34: ...i on40 Page 30 NOTES...

Страница 35: ...i on40 Page 31 NOTES...

Страница 36: ...ww coopersecurity co uk Product Support UK Tel 44 0 1594 541978 Available between 08 30 to 17 00 Monday to Friday Product Support Fax 01594 545401 email techsupport coopersecurity co uk Part Number 12...

Отзывы: