126
FX6000 InstAllAtIon And oPerAtIon MAnuAl
25-14683-C December 2019 www.eaton.com
Appendix
Micro input module wiring (MJIM)
Installation
1 . Fit the box in position using the mounting details below .
2 . Connect the unit according to the diagram below .
3 . Recommended Loop Cable Type: FIRETUF, FP200, MICC
ote:
n
No addressing of the interface is required . See control panel operation for details .
There are no serviceable parts so no maintenance procedures apply .
standard connections
ote:
n
1 . Only connect cable screen to its adjacent earth terminal
2 . The end of line resistor provided must always be fitted, even if the input is unused
3 . Monitored inputs can detect open or short circuit faults
IN +
Earth
Loop In+
Loop In-
Earth
Loop Out+
Loop Out-
IN -
EARTH
INPUT
LOOP
MJIM