52
FX6000 InstAllAtIon And oPerAtIon MAnuAl
25-14683-C December 2019 www.eaton.com
Installation
Input/outputs
Panel inputs
Class change: (OPTION NOT REQUIRED BY EN54)
A pair of terminals are provided for class change . By shorting these terminals
together (e .g . Switch, Time clock) the alarm will sound (Panel so loop
sounders only) . The Panel will not indicate a Fire . The alarm will cancel when the
short circuit is removed . If the short circuit is not removed the alarms will not cancel .
ote:
n
It is recommended that this input is wired using firetuf, fp200 or micc cable
with the screen connected to the earthing points in the panel enclosure
WArnInG
no VoltAGe sHould Be APPlIed to tHIs InPut
Panel outputs
Panel sounders: (OPTION 7 .8 EN54 PT 2)
Two pairs of outputs are provided . ONLY polarised equipment should be used .
Ensure the polarity of the connections are observed at all times and end of line
resistors (6K8 5%) are fitted for correct operation . The total alarm load across all
sounder outputs = 1 .5 Amp . All outputs are fused with 1 .6 Amp Glass fuse Alarm
devices should be spread equally across the 4 sounder circuits .
WArnInG
do not eXCeed tHe rAted outPut Current
--
++
Class change
Switch/c
ontactor
timer etc.
(Apply NO
voltage)
All sounders must be polarised
Both sounder circuits must
be terminated with a 6800 Ohm
end of line resistor