Installation and User manual for the 

conventional range of fire panels 

  

EATON

 www.eaton.com

Enable zone

Enter access code level 2, then press button

Yellow led of the first zone is flashing . 
Push button          several times until the yellow led of the relevant 

zone is flashing .
Push button          to enable the relevant zone .
Repeat this procedure to enable further disabled zones .

Disable sounders

Isolates sounder circuits from the system

Enter access code level, then press button  

The yellow LED of the zone 1 will light and the internal buzzer will 

pulse rapidly .
Push button         several times until both the disabled and sound-

ers disabled yellow LEDs are lit .
Push button         to confirm disable sounders .
The internal buzzer will pulse at a slow rate and the disabled and 

sounders disabled LEDs will remain lit .
To silence the internal buzzer

Enter access code level 2, then press button

Enable sounders

Enter access code level 2, then press button

Internal buzzer will rapidly pulse . 
Push button         several times until sounder LED turns off .
Push button         to confirm enable sounders

Self check detectors

This function is no longer available on new panels, however it 

may be available on existing panels.
Detector LED function (applies to self check detectors only)

Self check detectors incorporate self check intelligence enabling 

them to monitor their own status and to generate a fault signal at 

the panel in the event of a malfunction .
Should a detector develop a fault, the zone to which the detector 

is connected will indicate a zone fault and the status LED on the 

faulty detector will illuminate amber .
Should the detector fail completely, it is possible to instruct the 

panel to illuminate the LEDs of the healthy indicators instead .
To activate this function

Enter access code level 3 (engineer’s code)

Then press button

To cancel this mode

Enter access code level 3 (engineer’s code)

Then press button

The LED control facility can also be used to diagnose faults in the 

external zone wiring . Should a zone open circuit occur, activate 

the LED test mode as described above . The LEDs of all detec-

tors which still have a healthy connection to the panel will flash, 

making it easier to identify the location of the break .
Follow the instructions above to cancel LED indicator mode .

Содержание FX2202CPD

Страница 1: ...tallation and User manual for the conventional range of fire panels 2 and 4 zone panels Contents General 2 Wiring 2 Commissioning the system 5 Walk test facility 5 User Information 6 Self check detect...

Страница 2: ...double pole fused spur unit is used and marked FIRE ALARM DO NOT SWITCH OFF this should be for the sole use of the fire alarm Within the panel the mains supply should be isolated from the zone and ala...

Страница 3: ...Each zone circuit is supplied with an End of Line Monitor unit EOLM 1 All zone circuits must be terminated with an EOLM 1 connected at the end of the installed zone wiring taking care to observe the c...

Страница 4: ...y between C and P2 Continuity between C and P1 Continuity between C and P2 Figure 7 2 4 zone panel Auxiliary relay CAUTION POWER DOWN THE FIRE PANEL BEFORE YOU CHANGE ANY RELAY SETTINGS J1 Mode Panel...

Страница 5: ...he last call point in each zone operates correctly by using the supplied call point test key Reset the panel after each activation Fit all the detectors a zone at a time and check the panel shows heal...

Страница 6: ...resets detectors and resets control relays Enter access code level 2 Then press button followed by Ensure any smoke still in the activated detector is blown clear as the control panel will activate b...

Страница 7: ...under LED turns off Push button to confirm enable sounders Self check detectors This function is no longer available on new panels however it may be available on existing panels Detector LED function...

Страница 8: ...d batteries are no longer available as original equipment Carry out battery load test by disconnecting the mains supply and check the battery is capable of supplying the alarm sounder load by activati...

Страница 9: ...ttent Internal buzzer steady Fire General Fault Disable Power On Charger fault System fault Disable Fault zone Disable Fault counter cct Test Buzzer Normal condition Zone wiring open short Zone disabl...

Страница 10: ...V dc Fuse 5 Amp Glass Fuse F2 Located Main board Mode Configurable as Fire or Fault Relay Fire Relay Type N A Rating N A Fuse N A Located N A Mode N A Auxiliary Output V 24V dc Imax 30 mA Fuse Polyswi...

Страница 11: ...ecifications cont PSE Specification 2 Zone 4 Zone Mains Voltage V ac 230 10 15 Number of Batteries 1 Voltage V 12 Capacity aH 3 2 Standby Time 24 hour standby 30 minute alarm EOLM 1 Specification Oper...

Страница 12: ...Data PR000 00 513 04 Effective January 2018 Installation and User manual for the conventional range of fire panels Eaton is a registered trademark All other trademarks are property of their respectiv...

Отзывы: