Flexi -3G Installation & Commissioning Manual
Chapter 6. Installation of AC Cables
Document No: - 4493-CM-EN-10989402
Page 61 of 94
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved
1Ø+N+PE (A&B Feeds)
3Ø+N+PE (A&B Feeds)
3 core cable of 10mm² minimum
or
10mm² minimum PVC (80°C minimum)
singles in trucking or conduit.
5 core cable of 6mm² minimum
or
6mm² minimum PVC (80°C minimum)
singles in trucking or conduit.
Table 6-5 PBA-03 Cable Rating
6.6.2. AC Connection Information
Fig. 6-9 PBA-03 AC Rating Information Label
6.6.3. Installing Rectifiers in a PBA-03 System to Balance Phases
In order to provide a balanced load on the incoming AC supply, Install the quantity of rectifiers
required for the Power Supply Unit, with reference to the General Notes for Installing a Rectifier in
section 5.2. on page 49 and according to the table below.
AC Input
Terminals
Phase Connected
To
Rectifier Position in
Cabinet from Left to
Right
Installation Sequence
1
1
Ø1
2
7
Ø2 3
2
A
Ø3 4
3
Ø1 5
4
6
5
Ø2
7
8
8
6
B
Ø3
9
9
Table 6-6 Installing Rectifiers in a PBA-03 Power Supply Unit