Flexi -3G Installation & Commissioning Manual
Chapter 4. Battery Installation
Page 44 of 94
Document No: - 4493-CM-EN-10989402
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved
10 Battery Terminal Cover
14
Battery Cable Live (Grey) –
ve
15
Battery Cable Common
(Blue)+ve
Fig. 4-8 Replacing the Battery Terminal Covers
8.
Refit the Battery Terminal Cover to Battery 1.
9.
Check with a voltmeter that the negative terminal of battery 4 is more than 48V
negative of the positive terminal of battery 1.
10.
Measure the voltage across the Battery MCB and ensure that this is less than 6V.
If more than 6V, check the battery connections to the MCB.
15
14
10