Flexi -3G Installation & Commissioning Manual
Chapter 2. Flexi - 3G System General Description
Page 10 of 94
Document No: - 4493-CM-EN-10989402
Copyright © 2008-2009 Eaton Corporation. All Rights Reserved
2.1. Flexi – 3G Power Box Description
The Eaton Flexi - 3G Power Box is available in three versions: -
Fig. 2-1 PBA-01 Power Box
Fig. 2-2 PBA-02 Power Box
Fig. 2-3 PBA-03 Power Box
The PBA-01 Power Box
consists of
The PBA-02 Power Box
consists of
The PBA-03 Power Box
consists of
•
16.2kW Capacity Base
Power Box
•
16.2kW Capacity Base
Power Box
•
16.2kW Capacity Base
Power Box
•
650H x 600W x 450D
•
650H x 600W x 450D
•
650H x 600W x 450D
•
9 x APR48-3G Capability
•
9 x APR48-3G Capability
•
9 x APR48-3G Capability
•
SC200 Cont IOBGP-
00
•
SC200 Controller
•
SC200 Controller
•
AC Input Terminals only:-
•
Optional AC Input Isolator
•
AC Input Isolator
•
Separate A + B Terminals for
AC (4/5 rectifiers on A and 4
on B)
•
1PH AC Input (230Vac, 50-
60Hz, 1P + N + PE)
•
•
1PH AC Input (230Vac, 50-
60Hz, 1P + N + PE)
•
3PH AC Input (400Vac, 50-
60Hz, 3P + N + PE)
•
3PH AC Input (115/230Vac,
50-60Hz, 3P + PE) – 3 Wire
Delta
•
3PH AC Input (400Vac, 50-
60Hz, 3P + N + PE)
•
Optional Surge Module
•
Surge Module
•
•
•
2-Pole MCBs for each
Rectifier
•
•
Plastic Gland Plate for Top
Cable Entry
•
Plastic Gland Plate for Top
Cable Entry
•
Plastic Gland Plate for Top
Cable Entry