Enterprise Power Solutions Installation and Operation Guide
58
Copyright © 2008 Eaton Corporation. All Rights Reserved.
IPN 997-00012-56C September 2008
Step 6 - LVD Characterization Alarm
If there is no LVD Characterization alarm then ignore this step.
If the SC200 or SC100 indicates an
LVD Characterization Error
alarm then:
1
On the SC200 go to: Battery > LVDs > LVD1 > Options, or on the SC100 go
to: Menu > Configuration > Low Volts Disconnect
2
If available, select
Characterize With IOB Values
. Press
Enter
. No further
action is needed.
3
If
Characterize With IOB Values
if not available, the LVD must be
characterized. This will cause the LVD contactor to disconnect the battery
for a few seconds.
The load equipment will be powered by the rectifiers.
•
On the SC200 go to: Battery > LVDs > LVD1 > Options, or on the SC100
go to: Menu > Configuration > Low Volts Disconnect
•
Select
Characterize
. Press
Enter
.
The LVD contactor will disconnect and connect. When the characterization
is complete the LVD Characterization Error alarm will clear.
Procedure complete
Return the faulty SC200 or SC100 with a completed Equipment Incident Report on page