PDU.Input[2].Phase[x].PresentStatus.OverCurrent
AlarmL1
0 : No threshold trigged
1 : Warning low threshold trigged
2 : Critical low threshold trigged
3 : Warning high threshold trigged
4 : Critical high threshold trigged
-
RO
PDU.Input[2].Phase[x].PresentStatus.OverVoltage
AlarmL1
0 : No threshold trigged
1 : Warning low threshold trigged
2 : Critical low threshold trigged
3 : Warning high threshold trigged
4 : Critical high threshold trigged
-
RO
PDU.Input[2].Phase[x].ReactivePower
HideMeasure
Reactive Power Measurement.
dVA
R
RO
PDU.Input[2].Phase[x].Statistic[5].Energy
HideMeasure
Energy counter since ePDU start.
Wh
RO
PDU.Input[2].Phase[x].Statistic[5].ModuleReset
Command
Command to Reset the stat, this command does not put 0
in the counter but saves the current value of Energy timer
into the data ...Reset.Energy.
-
RW
PDU.Input[2].Phase[x].Statistic[5].Reset.Energy
HideMeasure
Energy saved at the instant the user resets the stat.
Wh
RO
PDU.Input[2].Phase[x].Statistic[5].Reset.Time
HideMeasure
Timestamp saved at the instant the user resets the stat.
s
RO
PDU.Input[2].Phase[x].Voltage
Measure
Voltage Measurement.
cV
RO
PDU.Input[2].PowerFactor
Measure
Ratio of active power / apparent power provided by the
input.
Value 0 to 100 for Cos PHI = 0.00 to 1.00
m%
RO
PDU.Input[2].PresentStatus.FrequencyOutOfRange
AlarmL1
0 : Frequency OK
1 : Frequency is out of +/- 3Hz tolerance
-
RO
PDU.Input[2].ReactivePower
Measure
Reactive Power Measurement.
It's the cumul of 1 or 3 phase measures.
dVA
R
RO
PDU.Input[2].Statistic[3].ActivePower
Measure
Power peak consumption since last reset.
When it is reset to 0 then at the same time the related
timestamp is updated with the current RTC value.
When it is detected higher than the value stored, so it
overwrites it.
dW
RO
PDU.Input[2].Statistic[3].ModuleReset
Command
Command to Reset the stat, this command put 0 in the max
and saves the current value of Timer into the data …Timer
and into ...Reset.Timer.
-
RW
PDU.Input[2].Statistic[3].Reset.Time
Measure
Timestamp saved at the moment where the statistic is
reset.
s
RO
PDU.Input[2].Statistic[3].Time
Measure
Timestamp saved at the moment where the statistic is
reset.
s
RO
PDU.Input[2].Statistic[5].Energy
Measure
Energy counter since ePDU start.
It cumulates the energy consumed on 1 or 3 phases.
Wh
RO