FUNCTION SPECIFICATIONS 

Items 

Specifications 

Remarks 

Control Method 

Stored program, cyclic scan system 

 

I/O Processing Method 

Batch processing method (when END command 
is executed) 

I/O refresh command is 
available 

Execution Speed 

Basic commands (several us) 

Application Commands 
(10~hundreds us) 

Program Language 

Co Ladder Logic + SFC 

Including the Step commands 

Program Capacity 

7,920 STEPS 

SRAM + Battery 

Commands 

32 Basic sequential commands 

168 Application commands 

Rela

y (bit 

mode)

 

X  External Input Relay 

X0~X177, octal number system, 128 
points 

Total 

256

points

Correspond to external I/P 
point

Y  External Output Relay 

Y0~Y177, octal number system, 128 
points 

Correspond to external O/P 
point

M

Auxiliary 

Relay

General 

M0~M511, 512 points (*1) 

Total 

4,096 

points

Contacts can switch to On/Off 
in program 

Latched 

M512~M999, 488 points (*3) 
M2000~M4095, 2,096 points (*3) 

Special 

M1000~M1999, 1,000 points (some are 
latched) 

T Timer 

100ms

T0~T199, 200 points (*1) 

Total 

256

points

When the timer that set by 
TMR command reaches the 
preset value, the T contact with 
the same number will be On. 

T192~T199 for Subroutine 
T250~T255, 6 points Accumulative (*4) 

10ms

T200~T239, 40 points (*1) 
T240~T245, 6 points Accumulative (*4) 

1ms 

T246~T249, 4 points Accumulative (*4) 

C Counter 

16-bit Count 
Up

C0~C95, 96 points (*1) 

Total 

250

points

When the counter that set by 
CNT (DCNT) command 
reaches the preset value, the C
contact with the same number 
will be On. 

C96~C199, 104 points (*3) 

32-bit Count 
Up/Dn 

C200~C215, 16 points (*1) 
C216~C234, 19 points (*3) 

32bit
High-speed 
Count Up/Dn 

C235~C245, 1 ph, 1 input, 9 points (*3) 
C246~C250, 1 ph, 2 input, 3 points (*3) 
C251~C254, 2 ph, 2 input, 3 points (*3) 

S

Step 
point

Initial Step 
Point

S0~S9, 10 points (*1) 

Total 

1,024 

points

Usage device of step ladder 
diagram (SFC) 
Latched Range: 
Start: D1214 (K512) 
End: D1215 (K895)   

Zero Point 
Reset 

S10~S19, 10 points (use with IST 
command) (*1) 

General 

S20~S511, 492 points (*1) 

Latched 

S512~S895, 384 points (*3) 

Alarm 

S896~S1023, 128 points (*3) 

Regi

ster (W

ORD d

a

ta

T

Current Value of the 
Timer 

T0~T255, 256 points 

When the timer reaches the 
preset value, the contact of 
timer will be On. 

C

Current Value of the 
Counter 

C0~C199, 16-bit counter, 200 points 
C200~C254, 32-bit counter, 50 points 

When the counter reaches the 
preset value, the contact of 
counter will be On. 

D

Data 
Register 

General 

D0~D199, 200 points (*1) 

Total 

5,000 

points

Can be memory area for 
storing data.    E and F can be 
used as the special purpose of 
index indication. 

Latched 

D200~D999, 800 points (*3) 
D2000~D4999, 3,000 points (*3) 

Special 

D1000~D1999, 1,000 points 

Index 

E0~E3, F0~F3, 8 points (*1) 

None

File Register 

0~1,599 (1,600 points) (*4) 

Expansion register for storing 
data. 

Pointer

 

N

For Master Control 
Nested Loop 

N0~N7, 8 points 

Control point of master control 
nested loop 

P

For CJ, CALL 
Commands

P0~P255, 256 points 

The location point of CJ, CALL.

I

Inte

rrup

t Se

rvi

ce

 

External Interrupt

I001 (X0), I101 (X1), I201 (X2), I301 (X3), I401 
(X4), I501 (X5); 6 points (all are rising-edge 
trigger) 

The location pointer of interrupt 
subroutine 

Time Interrupt 

I6

 (1ms), I7

 (1ms), (

1~99ms) 

ϭϭ

ϭϭ

ϭϭЈ

Hi-speed Counter  I010, I020, I030, I040, I050, I060; 6 points 

Communication 

I150, 1 point 

Con

s

ta

n

K Decimal 

K-32,768 ~ K32,767 (16-bit operation) 
K-2,147,483,648 ~ K2,147,483,647 (32-bit operation) 

H  Hexadecimal 

H0000 ~ HFFFF (16-bit operation), H00000000 ~ HFFFFFFFF (32-bit operation) 

Programming Port 

COM1: RS-232, COM2: RS-485 (Master/Slave), Can be used at the same time. 

Analog Volume / Perpetual 
Calendar (RTC) 

ELC built-in 2 points VR / ELC built-in RTC 

Special Expansion Module 

Use the same modules of ELC series. (Max. 8 Expansion Unit points) 