O & M Manual for the EGS Metered, Service
Entrance Automatic Transfer Switch with Relay Control
Eaton Corporation www.eatoncanada.ca
5.4 Manual Operation
Warning
DO nOT aTTEMPT TO ManUaLLY OPEraTE THE aTS WiTH THE UTiLiTY
Or gEnEraTOr aVaiLaBLE.
Warning
HigH VOLTagES arE PrESEnT in anD arOUnD TranSFEr SWiTCH
EQUiPMEnT. BEFOrE aTTEMPTing TO ManUaLLY TranSFEr,
DiSCOnnECT THE LinE POWEr FrOM THE EQUiPMEnT BEing SErViCED
BY OPEning anD LOCKing OUT, iF POSSiBLE, THE nEXT HigHEST
DiSCOnnECT DEViCE. FaiLUrE TO FOLLOW THiS PrOCEDUrE COULD
CaUSE SEVErE PErSOnaL inJUrY anD/Or DEaTH.
aLWaYS TUrn THE UTiLiTY POWEr OFF anD TUrn THE gEnEraTOr (iF
a gEnEraTOr) COnTrOL SELECTOr SWiTCH TO THE “OFF” POSiTiOn
BEFOrE aTTEMPTing a ManUaL TranSFEr.
Warning
inSUrE THE DEaDFrOnT iS inSTaLLED PriOr TO EnErgiZing THE
TranSFEr SWiTCH.
To Manually Operate
Step 1: Disconnect all sources of power.
Step 2: Locate the manual lever between the solenoids..
Step 3: Locate the handle used to manually transfer the switch.
Step 4: Attach the handle to the manual lever.
Step 5: Move the lever up to go to utility or move the lever down to go to
generator.
Step 6: Reconnect the power.
Figure 13. ATS Manual Operating Lever.
Figure 14. ATS Manual Operating Handle.