Instruction Booklet  

IB0162063EN

Effective January 2014

O & M Manual for the EGS Metered, Service

Entrance Automatic Transfer Switch with Relay Control

Eaton Corporation www.eatoncanada.ca

4.5 Generator & Load Power Cable Connection

Warning

POWEr COnDUCTOrS MaY HaVE VOLTagE PrESEnT THaT Can CaUSE 

SEVErE PErSOnaL inJUrY Or DEaTH.  DE-EnErgiZE aLL POWEr 

Or COnTrOL CirCUiT COnDUCTOrS TO BE COnnECTED TO THE aTS 

EQUiPMEnT BEFOrE BEginning TO WOrK WiTH THE COnDUCTOrS anD/

Or TErMinaTing THEM TO THE EQUiPMEnT

CaUTiOn

TO HELP PrEVEnT COMPOnEnT DaMagE Or FUTUrE MaLFUnCTiOnS, 

USE EXTrEME CarE TO KEEP COnTaMinanTS OUT OF THE aTS 

EQUiPMEnT WHEn MaKing THE POWEr CaBLE COnnECTiOnS.

Test all power cables prior to connection to the unit to ensure that 

the conductors or cable insulation has not been damaged while 

being pulled into position.
Power cables are to be connected to solderless, screw type lugs 

located on the contactor assembly.  Verify that the lugs supplied will 

accommodate the power cables being used.  Also verify that the 

cables comply with all local electrical codes.  Standard ATS equip-

ment, as supplied from the factory, will accommodate the wire sizes 

shown in Table 3.

Table 3.  Wire Sizes for ATSs.

Transfer Switch

amp rating

Contactor Lug

Size range

number of Cables

per Phase

100

#14 - 1/0 AWG

1

200

#4 AWG - 300 MCM 

1

CaUTiOn

iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT 

anD SUBSEQUEnT EQUiPMEnT FaiLUrE.

ote: 

N

Tighten the cable lugs to the torque identified on the label 

affixed to the unit’s door.

Connect cables as follows (see Figure 10, and Table 3):

• 

The generator power cables to the generator lugs on the contac-

tor assembly.

• 

The load power cables to the load lugs on the contactor assem-

bly.

• 

The generator neutral cable to the generator neutral lug on the 

neutral bar assembly.

• 

The load neutral cable to the load neutral lug on the neutral bar 

asssembly.

• 

The generator and load ground cable to the generator and load 

ground lugs on the ground bar assembly.

Warning

FaiLUrE TO PrOPErLY COnnECT THiS TranSFEr SWiTCH PEr nFPa 70, 

THE naTiOnaL ELECTriC CODE, MaY rESULT in PrODUCT FaiLUrE, FirE, 

LOSS OF PrOPErTY, LOSS OF LiFE, ETC. 

Figure 9. Generator & Load Power Cable Connection Locations.

4.6 Wiring

Warning

POWEr COnDUCTOrS anD COnTrOL Wiring MaY HaVE VOLTagE 

PrESEnT THaT Can CaUSE SEVErE PErSOnaL inJUrY Or DEaTH.  

DE-EnErgiZE aLL POWEr Or COnTrOL CirCUiT COnDUCTOrS BEFOrE 

BEginning TO PErFOrM anY Wiring aCTiViTY TO Or WiTHin THE aTS 

EQUiPMEnT.

CaUTiOn

CHECK THE aTS EQUiPMEnT naMEPLaTE FOr raTED VOLTagE.  iT 

SHOULD BE THE SaME aS THE UTiLiTY anD gEnEraTOr LinE VOLTagES.  

OPEraTing THE EQUiPMEnT On iMPrOPEr VOLTagE Can CaUSE 

EQUiPMEnT DaMagE.

Generator 

& Load 

Neutral

Generator 

& Load 

Hots

Содержание EGS Series

Страница 1: ...uipment Description 5 4 Installation and Wiring 8 5 Functional Testing 12 6 Adjustments 13 7 Maintenance and Component Replacement 14 Effective January 2014 Instruction Booklet IB0162063EN O M Manual...

Страница 2: ...e proceeding If fur ther information is required by the purchaser regarding a particular installation application or maintenance activity please contact an authorized Eaton sales representative or the...

Страница 3: ...ear Conversely if connected to the generator power source and the generator power source fails while the utility power source is still unavailable the ATS remains connected to the generator power sour...

Страница 4: ...e when it is within its undervoltage setpoint ranges for the nominal voltage setting Connected Connected is defined as when the input is shorted by an external contact or connection Failed or Fails A...

Страница 5: ...site and ready to be installed the packaging material can be removed Refer to Section 4 of this manual for specific installation instructions 2 3 Storage Although well packaged this equipment is not s...

Страница 6: ...configuration or an under ground one Twin 2 hub openings on the top of the enclosure will accept a standard Myers type hub The assembly ships with removable hub closure plates installed over these ope...

Страница 7: ...e lugs sup plied will accommodate the power cables being used Also verify that the cables comply with all local electrical codes Standard ATS equipment as supplied from the factory will accommodate th...

Страница 8: ...range number of Cables per Phase 100 14 1 0 AWG 1 200 4 AWG 300 MCM 1 CaUTiOn iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT anD SUBSEQUEnT EQUiPMEnT FaiLUrE ote N Tighten the cable lugs to...

Страница 9: ...ector switch to the OFF position to prevent an unwanted generator start Control wiring such as the generator transfer wires and utility sensing must be run in a separate conduit from the power cables...

Страница 10: ...ontactor will automatically switch to the UTILITY position WARNING CONTACT WITH ENERGIZED COMPONENTS WILL CAUSE ELECTRICAL SHOCK CAPABLE OF PRODUCING SEVERE PERSONAL INJURY OR DEATH USE EXTREME CAUTIO...

Страница 11: ...DEVICE FAILURE TO FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL INJURY AND OR DEATH ALWAYS TURN THE utility POWER OFF AND TURN THE generator IF A GENERATOR CONTROL SELECTOR SWITCH TO THE oFF POSI...

Страница 12: ...inspection and or maintenance Disconnect the line power from the equipment being serviced by opening next highest disconnect device Make certain that any accessory control power is switched off b Ins...

Страница 13: ...IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Figure 15 Wiring Diagram for the EGSC ATS Show...

Страница 14: ...B0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca 7 3 Maintenance Log Date Action Example 01 01 1...

Страница 15: ...DEATH ALWAYS TURN THE UTILITY SOURCE 1 POWER OFF AND TURN THE GENERATOR SOURCE 2 CONTROL SELECTOR SWITCH TO THE OFF POSITION BEFORE ATTEMPTING TO REPLACE ANY COMPONENTS NOTICE Apply utility source 1 p...

Страница 16: ...thRelayControl Eaton Corporation www eatoncanada ca Figure 16 Dimensions and Plan View of a Service Entrance EGS in 200A 2 2 Hub Openings 5 90 150mm 5 90 150mm 7 81 198mm 36 19 919mm 29 47 749mm 4 69...

Страница 17: ...17 Instruction Booklet IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Notes...

Страница 18: ...ractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equ...

Отзывы: