background image

4

Instruction Booklet  

IB0162063EN

Effective January 2014

O & M Manual for the EGS Metered, Service

Entrance Automatic Transfer Switch with Relay Control

Eaton Corporation www.eatoncanada.ca

The benefits of the SE configuration are:

• 

Combined service disconnect and over-current protection in the 

ATS reduces the overall equipment and installation costs.

• 

Fewer components and power connections reduce maintenance 

requirements.

1.3 Transfer Switch Catalogue Number Identification

ATS equipment catalogue numbers provide a significant amount 

of relevant information pertaining to a specific piece of equipment.  

The Catalogue Number Identification Table (see Table 1) provides the 

required interpretation information.

Table 1.  ATS Catalogue Numbering System.

1.4 Environmental and Operational Conditions

Normally, an ATS is applied indoors in an electrical equipment room.  

It can also be used for normal outdoor applications (with standard 

type 3R enclosure) where the equipment is subject to falling rain, 

freezing temperatures, and 95% humidity (non-condensing).  The 

ambient temperature range for operation is between -20 and 70°C 

(-4 and 158°F)..

E   GSC   200A   M   SE      

Metering

Metered 

ampere 

rating

100A=100A 

200A=200A

Type

Generator 

Switch 

with  

Relay

Manufacturer

Eaton

1.5 Glossary

With respect to their use within this document and as they relate to 

transfer switch and controller operation, the following terminology is 

defined.

available

A source is defined as “available” when it is within its undervoltage 

setpoint ranges for the nominal voltage setting.

Connected

Connected is defined as when the input is shorted by an external 

contact or connection.

Failed or Fails

A source is defined as “failed” when it is outside of the applicable 

voltage setpoint ranges for the nominal voltage and for a time 

exceeding 0.5 seconds after the time delay emergency fail (TDEF) 

time delays expires.

Failsafe

Failsafe is a feature that prevents disconnection from the only avail-

able power source and also forces a transfer or re-transfer operation 

to the only available power source.

re-Transfer

Re-transfer is defined as a change of the load connection from the 

Generator to the Utility.

Utility

Utility is the primary source (normal source, normal power source, 

or normal).

generator

Generator is the secondary source (generator emergency source, 

emergency power source, emergency, standby, or backup source).

Utility: Failed or Fails

Utility is defined as “failed” when it is outside of its undervoltage 

setpoint ranges for the nominal voltage and frequency setting.

generator: Failed or Fails

Generator is defined as “failed” when it is outside of its undervolt-

age/underfrequency/overfrequency (if applicable) setpoint ranges 

for the nominal voltage and frequency setting for a time exceeding 

0.5 seconds after the Time Delay Emergency Fail (TDEF) time delay 

expires.

Transfer

Transfer is defined as a change of the load connection from the 

Utility to the Generator power source.

Unconnected

Unconnected is defined as when the input is not shorted by an 

external contact or connection.

Service 

 Entrance

Canadian 

Service Entrance 

Approved

Содержание EGS Series

Страница 1: ...uipment Description 5 4 Installation and Wiring 8 5 Functional Testing 12 6 Adjustments 13 7 Maintenance and Component Replacement 14 Effective January 2014 Instruction Booklet IB0162063EN O M Manual...

Страница 2: ...e proceeding If fur ther information is required by the purchaser regarding a particular installation application or maintenance activity please contact an authorized Eaton sales representative or the...

Страница 3: ...ear Conversely if connected to the generator power source and the generator power source fails while the utility power source is still unavailable the ATS remains connected to the generator power sour...

Страница 4: ...e when it is within its undervoltage setpoint ranges for the nominal voltage setting Connected Connected is defined as when the input is shorted by an external contact or connection Failed or Fails A...

Страница 5: ...site and ready to be installed the packaging material can be removed Refer to Section 4 of this manual for specific installation instructions 2 3 Storage Although well packaged this equipment is not s...

Страница 6: ...configuration or an under ground one Twin 2 hub openings on the top of the enclosure will accept a standard Myers type hub The assembly ships with removable hub closure plates installed over these ope...

Страница 7: ...e lugs sup plied will accommodate the power cables being used Also verify that the cables comply with all local electrical codes Standard ATS equipment as supplied from the factory will accommodate th...

Страница 8: ...range number of Cables per Phase 100 14 1 0 AWG 1 200 4 AWG 300 MCM 1 CaUTiOn iMPrOPEr POWEr CaBLE COnnECTiOnS Can CaUSE EXCESSiVE HEaT anD SUBSEQUEnT EQUiPMEnT FaiLUrE ote N Tighten the cable lugs to...

Страница 9: ...ector switch to the OFF position to prevent an unwanted generator start Control wiring such as the generator transfer wires and utility sensing must be run in a separate conduit from the power cables...

Страница 10: ...ontactor will automatically switch to the UTILITY position WARNING CONTACT WITH ENERGIZED COMPONENTS WILL CAUSE ELECTRICAL SHOCK CAPABLE OF PRODUCING SEVERE PERSONAL INJURY OR DEATH USE EXTREME CAUTIO...

Страница 11: ...DEVICE FAILURE TO FOLLOW THIS PROCEDURE COULD CAUSE SEVERE PERSONAL INJURY AND OR DEATH ALWAYS TURN THE utility POWER OFF AND TURN THE generator IF A GENERATOR CONTROL SELECTOR SWITCH TO THE oFF POSI...

Страница 12: ...inspection and or maintenance Disconnect the line power from the equipment being serviced by opening next highest disconnect device Make certain that any accessory control power is switched off b Ins...

Страница 13: ...IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Figure 15 Wiring Diagram for the EGSC ATS Show...

Страница 14: ...B0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca 7 3 Maintenance Log Date Action Example 01 01 1...

Страница 15: ...DEATH ALWAYS TURN THE UTILITY SOURCE 1 POWER OFF AND TURN THE GENERATOR SOURCE 2 CONTROL SELECTOR SWITCH TO THE OFF POSITION BEFORE ATTEMPTING TO REPLACE ANY COMPONENTS NOTICE Apply utility source 1 p...

Страница 16: ...thRelayControl Eaton Corporation www eatoncanada ca Figure 16 Dimensions and Plan View of a Service Entrance EGS in 200A 2 2 Hub Openings 5 90 150mm 5 90 150mm 7 81 198mm 36 19 919mm 29 47 749mm 4 69...

Страница 17: ...17 Instruction Booklet IB0162063EN Effective January 2014 O MManualfortheEGSMetered Service EntranceAutomaticTransferSwitchwithRelayControl Eaton Corporation www eatoncanada ca Notes...

Страница 18: ...ractual agreement between the parties This literature is not intended to and does not enlarge or add to any such contract The sole source governing the rights and remedies of any purchaser of this equ...

Отзывы: