background image

Fitting Incoming Switch 

EMS1253 & EMS1253N  

Before fitting the switch ensure the 
terminals are fully open. Locate the 
switch onto the stabs ensuring the din 
rail clip is hooked over the mounting 
bracket.  Tighten the terminals  
to 2.4Nm 

Mounting bracket 

Din rail mounting clip 

Fitting Neutral Link assy- 300960  

Slide the neutral assembly into position with the 
mounting bracket hook engaged in the incomer 
mount.  Bolt the neutral copper connection to the 
busbar with the M5 x 12 fixing to 4.5Nm.  

Inner cover Cutaway for 4P Incomer 

When a 4 pole incomer is fitted the cutaway on 
the inner cover needs to be removed .  

Incomer mount 

Mounting bracket hook 

4.5Nm 

Single Phasing Kit - 300969  

Position the two comb busbars back to back 
and fit in the L1/L2/L3 fork terminals of the 
switch on the incoming side.  

2.4Nm 

Отзывы: