Surge Supression Device - 300961 type 1 and 300962 type 1&2
Before Installation:
Verify that the system is wired in a Three Phase Star configuration and that the voltage rating of the system matches the
voltage rating of the SPD as shown on the label.
If the Neutral to Earth voltage is greater than 5 VAC, then a problem may exist in the electrical system. The SPD may be installed; however, a
qualified person should be consulted to correct the problem.
Installation Instructions:
•
Fit SPD mounting bracket assembly to the back plate in the position shown
•
Fit 63A 4P MCB onto the stabs with the back end hooked on the din rail whilst
fitting the SPD device on the din rail next to it. Tighten the MCB terminals to 2.4Nm
•
Connect the EARTH wire to the nearest bolt on common earth.
Energise the System.
The Indicator should remain green. If the indicator turns RED,
de-energise and contact the Technical Services department.
2.4Nm
Separation Shield - 300965
In some arrangements, when the distribution board is used in a cluster, a 20mm spacer
is required to allow the bottom and top of the boards to be flush
A separation shield is required when
boards are mounted on top of each other and a barrier is required between them.
Position the separation shield
inside the board and fix with
M5 screws provided.
Alignment Spacer- 300966
Fit the spacer to the top or bottom of the board and
fix with M5 screws. The removed Distribution board
gland plate can be refitted to the spacer if required.
20mm
spacer
SPD mounting
bracket assembly
Remove shield from stabs
before fitting the SPD
feeder MCB
H630 x W440
x D130 mm
H1260 x W440
x D130 mm
H900 x W440
x D130 mm