EM, feedback circuit-
monitoring
353
02/16 MN05013001Z EN
Tabelle 11: Diagnostics-/-Error codes
Further information on these outputs is provided in section
“Common features”, page 348.
Coils and contacts
Function block coils initiate the functions of the function
block and monitor the connected safety transmitters.
The contacts of a safety function block confirm the enable
conditions present, selected operating modes or indicate
errors.
Coils
The EM..OC function block coil is used to start the moni-
toring function of the function block.
You can address the coil, for example, with an Enable
contact of a different safety function block.
The EM..FL function block coil monitors the signal of the
feedback loop in the safety circuit diagram.
The Reset coil EM..RE resets the function block in Manual
Start (MST) and Controlled Start (CST) operating modes and
starts normal operation. It is used in the safety circuit
diagram.
Status number
Plain text
Hexadecimal (0–F)
decimal (0-9)
0000
0000
No Enable.
2001
8193
Enable issued; waiting for OC-/FL input.
2003
8195
Waiting for rising edge at Reset.
2004
8196
Waiting for falling edge at Reset.
2007
8199
Waiting until feedback circuit closed.
8001
32769
No fault detected in feedback circuit (QS = 1).
801A
32794
Waiting until feedback circuit open.
F00C
61452
Error: Reset and OC operated on function block startup.
F011
61457
Error: Feedback circuit not opened after time.
F012
61458
Error: Feedback circuit not closed after time.
Содержание easySafety
Страница 1: ...Manual Control relay suitable for safety circuits Safety ES4P 02 16 MN05013001Z EN ...
Страница 4: ...2 ...
Страница 42: ...38 02 16 MN05013001Z EN ...
Страница 80: ...Installation 76 02 16 MN05013001Z EN ...
Страница 112: ...108 02 16 MN05013001Z EN ...
Страница 606: ...602 02 16 MN05013001Z EN ...