11. Connection to other devices
11.4 Modbus TCP
Fault Code
1 byte
0x83 ; Read Holding Registers
Exception Code
1 byte
02 or 03 or 04
Exception Code 02 = Starting address is invalid, i.e.:
l
0 (the user keeps specifying addresses as one-based addresses)
l
Undefined* (please refer to the "Modbus map" table) or
l
Un-enabled*
Exception Code 03 = The number of inputs is not >= 0x0001 and <= 0x07D0
Exception Code 04 = (Error in server) n.a.**
If no analog I/O is physically present (e.g., analog I/O smart modules missing or faulty),
the image table (values = 0) will still be delivered to the client. No check, no error mes-
sage.
*For an error message, it is sufficient if only one of the requested addresses is not
unlocked or is invalid.
**A read operation always returns consistent data from the image table, since this data
is protected from other modules by semaphores. In other words, as of this writing,
there is no known criterion for a "read holding registers" error in the server.
Read Input Registers 0x04:
In the event of an error, Modbus TCP will send an error frame.
Fault Code
1 byte
0x84 ; Read Input Registers
Exception Code
1 byte
02 or 03 or 04
Exception Code 02 = Starting address is invalid, i.e.:
l
0 (the user keeps specifying addresses as one-based addresses)
l
Undefined* (please refer to the "Modbus map" table) or
l
Un-enabled*
Exception Code 03 = The number of inputs is not >= 0x0001 and <= 0x07D0
Exception Code 04 = (Error in server) n.a.**
If no analog I/O is physically present (e.g., analog I/O smart modules missing or faulty),
the image table (values = 0) will still be delivered to the client. No check, no error mes-
sage.
*For an error message, it is sufficient if only one of the requested addresses is not
unlocked or is invalid.
**A read operation always returns consistent data from the image table, since this data
is protected from other modules by semaphores. In other words, as of this writing,
there is no known criterion for a "read input registers" error in the server.
554
easyE4
11/18 MN050009 EN www.eaton.com
Содержание easyE4 series
Страница 1: ...Manual 11 18 MN050009 EN easyE4 Manual...
Страница 4: ......
Страница 16: ...12 easyE4 11 18 MN050009 EN www eaton com...
Страница 22: ...0 1 About this manual 18 easyE4 11 18 MN050009 EN www eaton com...
Страница 40: ...1 easyE4 control relays description 1 10 Safety regulations 36 easyE4 11 18 MN050009 EN www eaton com...
Страница 169: ...easyE4 11 18 MN050009 EN www eaton com 165...
Страница 462: ...6 Function blocks 6 4 Timing and counter relay example 458 easyE4 11 18 MN050009 EN www eaton com...
Страница 490: ...7 System settings 7 16 Time and Date setting 486 easyE4 11 18 MN050009 EN www eaton com...
Страница 520: ...9 easyE4 inside 9 7 NET network 516 easyE4 11 18 MN050009 EN www eaton com...
Страница 524: ...10 Diagnostics messages of the operating system 10 2 Diagnostics buffer 520 easyE4 11 18 MN050009 EN www eaton com...
Страница 570: ...11 Connection to other devices 11 6 E mail function 566 easyE4 11 18 MN050009 EN www eaton com...
Страница 578: ...12 Faults 12 4 Functionality of the NET faulty 574 easyE4 11 18 MN050009 EN www eaton com...
Страница 582: ...13 Maintenance 13 3 Storage transport and disposal 578 easyE4 11 18 MN050009 EN www eaton com...
Страница 594: ...590 easyE4 11 18 MN050009 EN www eaton com...
Страница 614: ...610 easyE4 11 18 MN050009 EN www eaton com...