6. Function blocks
6.1 Manufacturer function blocks
Parameter error due to incorrect number or offset definition
Incorrect parameters are indicated whilst the program is running via the E1 - E3 error
outputs.
Parameter errors of this kind occur, for example, if the number of elements to be trans-
ferred exceeds the source or destination range, or when, due to an offset error, the
source and destination range are outside of the available marker range.
Transfer function blocks always copy or initialize marker
bytes, and never marker words or double words. This transfer
behavior does not depend on the values at I1 and I2 (source
address and destination address). You can copy a marker
double word, e.g., MD 12 to MD 96, by copying 4 marker bytes
with the function block.
The function block and its parameters
Function block inputs
Description
Note
(Bit)
EN
1: Activates the function block.
The checkbox for the
Function block release by EN is neces-
sary
parameter must first be enabled
T_
Triggering the transfer on a rising edge
(DWord)
I1
Source address
Offset to marker byte MB01 when using
for the definition one of the afore-
mentioned operands
I2
Destination address
Offset to marker byte MB01 when using
for the definition one of the operands
stated in the table
NO
Number of elements to be initialized or copied.
Integer value range
Operating mode INI: 1…+1024 Byte
Operating mode CPY: 1…+1024 Byte
Assigning operands
You can assign the following operands to the function block inputs that are numeric
inputs.
Operands
Value inputs
Constant, timer constant
x
MD, MW, MB - Markers
x
NB, NW, ND - NET markers
x
nNB, nND, nND- NET markers
NET stations n
x
IA - Analog input
x
QA - Analog output
x
QV - QV - Numeric output of a FB
x
312
easyE4
11/18 MN050009 EN www.eaton.com
Содержание easyE4 series
Страница 1: ...Manual 11 18 MN050009 EN easyE4 Manual...
Страница 4: ......
Страница 16: ...12 easyE4 11 18 MN050009 EN www eaton com...
Страница 22: ...0 1 About this manual 18 easyE4 11 18 MN050009 EN www eaton com...
Страница 40: ...1 easyE4 control relays description 1 10 Safety regulations 36 easyE4 11 18 MN050009 EN www eaton com...
Страница 169: ...easyE4 11 18 MN050009 EN www eaton com 165...
Страница 462: ...6 Function blocks 6 4 Timing and counter relay example 458 easyE4 11 18 MN050009 EN www eaton com...
Страница 490: ...7 System settings 7 16 Time and Date setting 486 easyE4 11 18 MN050009 EN www eaton com...
Страница 520: ...9 easyE4 inside 9 7 NET network 516 easyE4 11 18 MN050009 EN www eaton com...
Страница 524: ...10 Diagnostics messages of the operating system 10 2 Diagnostics buffer 520 easyE4 11 18 MN050009 EN www eaton com...
Страница 570: ...11 Connection to other devices 11 6 E mail function 566 easyE4 11 18 MN050009 EN www eaton com...
Страница 578: ...12 Faults 12 4 Functionality of the NET faulty 574 easyE4 11 18 MN050009 EN www eaton com...
Страница 582: ...13 Maintenance 13 3 Storage transport and disposal 578 easyE4 11 18 MN050009 EN www eaton com...
Страница 594: ...590 easyE4 11 18 MN050009 EN www eaton com...
Страница 614: ...610 easyE4 11 18 MN050009 EN www eaton com...