42
Fault code: A004
Fault LED is flash
1 beep every 1 second
Alarm because of UPS
internal heat sink
temperature is too high.
Please contact your supplier
Fault code: A004
Fault LED is flash
1 beep every 1 second
Alarm because of
ambient temperature
high.
Check if the ambient
temperature exceed 50°C. if it is
normal,
please contact your
supplier
Fault code: A007
Fault LED is flash
1 beep every 1 second
Fans blocked
Please contact your supplier
Fault code: F207
Fault lamp lights long,
Beep continuous.
Bypass fault
Please contact your supplier
Fault code: A00E
Fault LED is flash
1 beep every 1 second
In parallel system
,
parallel cable disconnect
Check if the parallel cable
connect OK.
Fault code: A012, AC18
Fault LED is flash
1 beep every 1 second
Parallel system
,
UPS1
line ok
,
UPS2 line loss
Check the line input
Fault code: A00F, AC19
Fault LED is flash
1 beep every 1 second
Parallel system
,
UPS
mode
(
normal
,
converter
,
HE
)
different
Check UPS OP mode, Keep OP
mode be the same
Fault code: F811
Fault lamp lights long,
Beep continuous.
Negative output power
Please contact your supplier
Fault code: F00E
Fault lamp lights long,
Beep continuous.
parallel cable disconnect Check if the parallel cable
connect OK.
8.2 Silencing the alarm
Press the ESC (Escape) button 3s on the front panel display to silence the alarm.
Check the alarm condition and perform the applicable action to resolve the
condition. If the alarm status changes or press the ESC button 3s on the front
panel display, the alarm beeps again, overriding the previous alarm silencing.