22
Reset fault status
Clears active fault
Clear event log
Clears events
Restore factory set
Returns all settings to original values
Settings
Sets parameters
Event log
Event list
Identification
[Product type/model] / [Part/Serial number] /
[UPS/NMC firmware]
5.4 User settings
The following table displays the options that can be changed by the user.
Submenu
Available settings
Default settings
Password
Key the password
USER
language
[English][Deutsch][Español]
English
User
password
[disabled] [Enabled]
[disabled]
Audible alarm [enabled] [disabled]
[enabled]
Output voltage [208V] [220V] [230V] [240V]
Can be changed in Standby mode and
Bypass mode
[230V]
Output
frequency
[autosensing] [50HZ][60HZ]
[autosensing]
Power
strategy
[normal] [high efficiency] [converter]
[normal]
Auto bypass
[enabled] [disabled]
[enabled]
Auto restart
[enabled] [disabled]
Authorize the product to restart
automatically when mains recovers after
a complete battery discharge.
[enabled]
Dry in
[Disabled] [SON] [SOFF] [Maintain
bypass]
[Disabled]
Dry out
[Load powered] [On battery mode]
[Battery low] [Battery disconnected]
[Bypass output] [UPS normal]
[Load powered]
Start on
battery
[enabled] [disabled]
[enabled]