23
External
battery
modules
[0~20]
According to model
External
battery AH
setting
[0~300]
According to model
Battery
remaining time
[enabled] [disabled]
[enabled]
Charger
current
[0~4] 0~4A for standard model
[0~12] 0~12A for long backup model
[1.4A] for 6K
[2A] for 10K
[4A] for 6KS/10KS
Site wiring
fault alarm
[disabled] [enabled]
[disabled]
LCD contrast [-5 ~ +5]
[+0]
5.5 UPS startup and shutdown
Please make sure there is no load connected to the ups before the ups is
turned on, and take on the load one by one after the UPS is turned on.
Take off all of the connected loads before turning off the UPS.
Starting the UPS with utility
Verify that the total equipment ratings do not exceed the UPS capacity to
prevent an overload alarm.
Start the UPS with utility:
Check all the connection is correct.
Power on the UPS, the fan begins to rotate. After that, the LCD will show the
default UPS status summary screen.
Pressing button continuously for more than 1 second, the buzzer will beep
300ms, UPS starts to turn on.
A few seconds later, the UPS turns into Line mode. If the utility power is abnormal,
the UPS will transfer to Battery mode without output interruption of the UPS.
Starting the UPS on Battery