![Eaton Durant Eclipse 5775X-40 Series Скачать руководство пользователя страница 50](http://html1.mh-extra.com/html/eaton/durant-eclipse-5775x-40-series/durant-eclipse-5775x-40-series_installation-and-operation-manual_3810959050.webp)
50
OPTIONAL OUTPUTS
Analog Retransmission
Output signals:
4-20 mA (<750
Ω)
and 0-10 V (>2500
Ω)
Accuracy:
0.13% full scale and 100 PPM /°C (and 0.07%
full scale change over 4-20 mA load ranges
Isolation dielectric strength:
2300 VAC to signal inputs, relays, and AC power
inputs, 500 VAC to analog outputs and DC power
inputs
RS 485 Serial Communications
Baud Rate:
1200, 2400, 4800, 9600, or 19,200, programmable
Parity:
Even, odd, or no parity
Address Range:
00 to 99 decimal (00 indicates offline)
Protocol:
Opto 22
®
compatible
Isolation Dielectric Strength: 2300 VAC to signal inputs, relays, and AC power
inputs, 500 VAC to analog outputs and DC power
inputs
ENVIRONMENTAL
Operating Environment:
Indoor use to 2000 meters
Temperature:
Operating:
0 to 50°C
Storage:
-20 to 70°C
Humidity:
0 to 85% RH, non-condensing
Vibration:
2.5 g’s, 30 to 200 Hz
Shock:
30 g’s, 11 msec half sinewave
EMC:
Immunity to EN 50082-2 (Heavy Industrial)
Emissions to EN 50081-2 (Heavy Industrial)
Front Panel:
NEMA 4X when mounted with gasket provided
Agency Approval: UL, cUL listed, CE marked
CE EMC immunity and emissions requirements were met using
shielded wiring on the RS-485, analog output, and pulse input/
power lines. The shields were connected to earth ground at the
Eclipse end of the shields.
Polution Degree 2
Overvoltage category II
SPECIFICATIONS cont.