42
Starting and Stopping Batch Delivery
This function can only be performed with an Eclipse batch control. Totalizers do not
have this capability.
Normally, every batch will be manually started and will stop automatically when the
batch is complete. However, conditions may cause the operator to stop the delivery
before the batch is complete. If the operator manually stops a batch, he may resume
delivery from the point at which he stopped, or may simply terminate the batch.
To start a batch:
1.
Enter the batch final preset as shown on page 40.
2.
Reset the batch counter as explained in “Pushing the Reset Button.” If the
batch count value screen is displayed, it will go either to zero or to the batch
final preset value.
3.
Press the
Start
key,
Start
PGM
Durant
the display will show the start prompt for three seconds.
If the unit has not been reset since the last batch was delivered, one of the
following error messages will appear -
, or
, or
.
Reset the batch count and try again. If the batch final preset has been set to
zero, the following error message will appear -
. Enter a batch final
preset other than zero and try again.
RUN MODE cont.