manualshive.com logo in svg
background image

Effective July 2010

 

Instructional Leaflet

 IL8700C39-04

 Installed 

pick-up (Dial) setting

  rating 

amperes 

j

  plug
 amperes  a

k

  B

k

  C

k

  D

k

 

E

k

 

k

  (In)

 

100 

25 

30 

35 

40 

50 

60 

75 

100

  200 

50 

60 

70 

80 

100 

120 

150 

200

  250 

63 

75 

88 

100 

125 

150 

188 

250

  300 

75 

90 

105 

120 

150 

180 

225 

300

  400 

100  120 

140 

160 

200 

240 

300 

400

  600 

150  180 

210 

240 

300 

360 

450 

600

  800 

200  240 

280 

320 

400 

480 

600 

800

  1000 

250  300 

350 

400 

500 

600 

750 

1000

  1200 

300  360 

420 

480 

600 

720 

900 

1200

  1600 

400  480 

560 

640 

800 

960  1200  1200

  2000 

500  600 

700 

800 

1000  1200  1200  1200

  2400 

600  720 

840 

960 

1200  1200  1200  1200

  3200 

800  960  1120  1200  1200  1200  1200  1200

  4000  1000  1200  1200  1200  1200  1200  1200  1200
  5000  1200  1200  1200  1200  1200  1200  1200  1200

j

 Except as noted, tolerances on pick-up levels are ±10% of values 

shown in chart.

k

 Ground fault pick-up levels shown are nominal values when 

tested with external control power present. Without external con-
trol power, such as is the case with the Digitrip RMS 510, ground 
pick-up levels may exceed these values and be as high as the 
value shown for the “E” setting of that particular rating plug.

l

 Not applicable to Digitrip OPTIM. The ground fault pick-up setting 

is read directly from Digitrip OPTIM. These settings range from 
25% to 100% of the rating plug value up to a maximum NEC 
limitation of 1200 amperes.

Depending upon the installation requirements, alternate 
ground fault sensing schemes may be employed. Two 
popular methods include: Ground return and zero sequence. 
Either method can be employed with the Digitrip Trip Unit.

For either type application, a ring type current sensor, as il-
lustrated in Figure 7, is normally employed. For ground return 
sensing, the sensor is arranged to have the system “main 
bonding jumper” pass directly through the sensor. For zero 
sequence sensing methods, all phase and neutral conduc-
tors must pass through the sensor. 

Where multi-conductor cables are required for a particular 
circuit and the window opening in a single BYZ sensor is too 
small to accommodate all cables, separate BYZ sensors may 
be installed on each set of cables 
(3 phase, neutral) and the secondaries connected in paral-
lel. (Note: Proper polarity markings must be observed.) The 
resultant secondary current signal will be equivalent to a 
single BYZ sensor. 

The BYZ current sensor styles shown in Figure 7 are avail-
able for all previously mentioned applications. When either 
style sensor is used, the ground fault values shown in Table 
3 are not applicable and the values shown in Table 4 should 
be used. One of the reasons for using the BYZ current 

sensors is to improve the level of sensitivity. This being the 
case, then the ground fault functional pick-up setting should 
be placed on position “A.” The sensitivity of the ground ele-
ment for this kind of arrangement will depend upon the ratio 
of the BYZ sensor used. 

A variety of utilization schemes are available utilizing each of 
the above methods of ground fault sensing. Therefore, the 
individual installation requirements must be closely studied 
to insure proper application. 

5.5  Current Sensors

The three current sensors installed in the circuit breaker are 
located at the rear of the circuit breaker on the lower studs. 
The location is shown in Figure 3-1 of l.B. 694C694. They 
produce an output signal proportional to the load current 
and furnish the Digitrip Trip Assembly with the intelligence 
and energy to trip the circuit breaker when the time-current 
conditions exceed the functional protection settings. 

The continuous current rating for any frame size breaker can 
be changed by changing the rating plug. A complete tabula-
tion of available current sensors and rating plugs is given in 

 ratings   sensor ratings - amperes
  plug
  amps  200  300  400  600  800  1200 1600 2000 2400 3200 4000 5000

  100  6.3 
  200  12.5  8.3  6.3
  250 

 

10.4  7.8

  300 

 

12.5  9.4  6.3

  400 

 

  12.5  8.3  6.3

  600 

 

 

  12.5  9.4  6.3

  800 

 

 

 

  12.5  8.3  6.3

  1000 

 

 

 

 

  10.4  7.8  6.3

  1200 

 

 

 

 

  12.5  9.4  7.5  6.3

  1600 

 

 

 

 

 

  12.5  10  8.3  6.3

  2000 

 

 

 

 

 

 

  12.5 10.4  7.8  6.3

  2400 

 

 

 

 

 

 

 

  12.5  9.4  7.5

  3200 

 

 

 

 

 

 

 

 

  12.5  10  8.0

  4000 

 

 

 

 

 

 

 

 

 

  12.5 10.0

  5000   

 

 

 

 

 

 

 

 

 

  12.5

j

 Except as noted, tolerances on pick-up levels are ±10% of values 

shown in chart. 

k

 Ground fault pick-up levels shown are nominal values when 

tested with external control power present. Without external 
control power such as is the case with the Digitrip RMS 510 trip 
unit, ground pick-up levels can vary between the minimum and 
maximum values shown for each sensor rating. 

l

 For BYZ (100/5) sensor, multiply above values by two.

14

eaTOn CORPORaTIOn

 www.eaton.com

Table 3  Ground Current Pick-up Settings 

l

Table 4  Approximate Ground Fault Pick-up Amperes Using BYZ 
(50/5) Sensor and “A” Position Setting on Ground Fault  Pick-up 

j

 

k

 

l

Содержание Digitrip RMS Series

Страница 1: ...Potential Transformer Module 15 6 0 Testing 15 6 1 Functional Field Testing 15 6 1 1 Secondary Injection Testing 15 6 2 Performance Testing for Ground Fault Trip Units 18 6 2 1 Code Requirements 18 6...

Страница 2: ...ing every application or circumstance which may arise If any questions arise contact Eaton for further information or instructions 1 0 Supplementary Information The instructions contained in this book...

Страница 3: ...ies as the OPTIMizer Hand Held Programmer plus energy monitoring local remote indi cation and communications capabilities except that only the Hand Held Programmer can establish trip unit addresses Se...

Страница 4: ...Effective July 2010 Instructional Leaflet IL8700C39 04 Figure 2a Typical Digitrip RMSTrip Unit Display Panels Figure 2b Typical Digitrip OPTIMTrip Unit Display Panels 4 eaton corporation www eaton com...

Страница 5: ...ted using secondary currents provided by an Amptector Trip Unit test kit as illustrated in I L 33 791 Detailed instructions for testing trip units are given in the individual trip unit instruction lea...

Страница 6: ...test receptacles for external field testing mounted in the breaker Figures 4 and 5 4 2 Digitrip RMS 610 The Digitrip RMS 610 Trip Assembly consists of a Digitrip RMS 610 Trip Unit described in I L 29...

Страница 7: ...gnal Contact High Load Alarm X X X X X Long Delay Trip X X X X X Short Circuit Trip X X X X X Ground Fault Trip o o o o o Ground Alarm Integral Test Provisions X X X X Trip Unit Status Indication LED...

Страница 8: ...l Ground Fault GNDT l o l o Long Delay LDT l l Overtemperature TEMP l l External Trip EXTT l l Long Time Delay Pickup LDPU l l Over Range Trip ORNG l l Information Normal NORM l l Protection Settings...

Страница 9: ...ting a Potential Transformer Module and a Power Relay Module mounted as shown in Figures 4 and 5 The Digitrip RMS 810 Trip Unit performs all the functions of the Digitrip RMS 610 Trip Unit with the ad...

Страница 10: ...ze a fixed interchangeable rating plug to establish the continuous trip rating of the circuit breaker Rating plugs are interlocked to prevent use between different circuit breaker types Precise system...

Страница 11: ...6 for OPTIM 750 In addition OPTIM 1050 Trip Units are capable of pro viding data on power quality and permit energy monitoring Energy Monitoring 1 Peak demand kW 2 Present demand kW 3 Forward energy...

Страница 12: ...power required 5 2 Digitrip Trip Assembly The basic Digitrip Trip Assembly as shown in Figures 4 and 5 includes the following which could vary slightly depending upon the exact model of the Digitrip T...

Страница 13: ...l sensing scheme which vectorially sums the outputs of the individual phase current sensors As long as the vecto rial sum is zero then no ground fault exists If the system neutral is grounded and a ne...

Страница 14: ...t signal will be equivalent to a single BYZ sensor The BYZ current sensor styles shown in Figure 7 are avail able for all previously mentioned applications When either style sensor is used the ground...

Страница 15: ...FORMER MODULE DISCONNECT PLUG IS CONNECTED DEATH OR SEVERE PERSONAL INJURY MAY RESULT AND THE POTENTIAL TRANSFORMER MODULE AND TRIP UNIT WILL BE DAMAGED REMOVE THE PTM DISCONNECT PLUG PRIOR TO PERFORM...

Страница 16: ...AMPTECTORTEST KIT STYLES 140D481G02R 140D481G02RR OR 140D481G03 IN CONJUNCTION WITH A DIGITRIP ADAPTER STYLE 8779C02G01 SHOULD BE USED UNMODIFIED AMPTECTORTEST KIT STYLES 140D481G01 AND 140D481G02 SH...

Страница 17: ...harge of the Building s Electrical Installation in order to be available to the Authority having Jurisdiction Test Date Circuit Results Breaker Number Figure 9 Typical PerformanceTest Record Form Effe...

Страница 18: ...ource apply a test current of 125 of the Digitrip Ground Fault Trip Unit pickup setting through one phase of the circuit breaker as shown in Figure 8a This should cause the breaker to trip in less tha...

Страница 19: ...Curves for Types DSII and DSLII Circuit Breakers with Digitrip OPTIM 750 and 1050 Trip Units SC 6275 95 Typical Long Delay I2 t Short Delay I2 t Types DSII and DSLII rated up to 1200A SC 6276 95 Typic...

Страница 20: ...______ By____________________________ Figure 10 TypicalTrip Function Record Digitrip Automatic trip operation record Circuit No Address Breaker Shop Order References ________________ _________________...

Страница 21: ...Effective July 2010 Instructional Leaflet IL8700C39 04 21 eaton corporation www eaton com...

Страница 22: ...Effective July 2010 Instructional Leaflet IL8700C39 04 22 eaton corporation www eaton com...

Страница 23: ...Effective July 2010 Instructional Leaflet IL8700C39 04 23 eaton corporation www eaton com...

Страница 24: ...icies or other contractual agreement between Eaton and the purchaser THERE ARE NO UNDERSTANDINGS AGREEMENTS WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR...

Отзывы: