DC1 is designed to meet the UL requirements. In order to ensure full compliance, the following must be fully observed.

Input Power Supply Requirements

Supply Voltage

DC1-S1…

110 - 115 RMS Volt for 115 Volt rated units, ±10 % variation allowed. 115 Volt RMS Maximum

DC1-S2…

200 - 240 Volt for 230 Volt rated units, ±10 % variation allowed. 240 Volt RMS Maximum

Imbalance

Maximum 3 % voltage variation between phase – phase voltages allowed
All DC1 units have phase imbalance monitoring. A phase imbalance of > 3 % will result in the drive tripping.

For input supplies which have supply imbalance greater than 3 % Eaton Drives recommends the installation of input line reactors.

Frequency

50 - 60 Hz ±5 % Variation

Short Circuit Capacity

Voltage Rating

Min. kW (HP)

Max. kW (HP)

Maximum supply short-circuit current

115 V

0.37 (0.5)

0.75 (1)

100 kA rms (AC)

230 V

0.37 (0.5)

1.1 (1.5)

100 kA rms (AC)

All the drives in the above table are suitable for use on a circuit capable of delivering not more than the above specified maximum

short-circuit Amperes symmetrical with the specified maximum supply voltage.

General Requirements

Mechanical Installation Requirements

All DC1 units are intended for indoor installation within controlled environments which meet the condition limits:

– for IP20 (NEMA 0) units, installation is required in a pollution degree 1 environment.

– for IP66 (NEMA 4X) units, installation in a pollution degree 2 environment is permissible.

Ambient temperature range

Operational

-10 °C to 50 °C (14 °F to 122 °F), to 60 °C (140 °F) with rerating (frost an condensation free)

Storage and Transportation

-40 °C to 60 °C (-40 °F to 140 °F)

Relative Humidity

< 95 % (non condensing). Drive must be Frost and moisture free at all times.

Max. altitude for rated operation

1000 m. Derate above 1000 m: 1 % / 100 m. Installation above 2000 m is not UL approved.

Electrical Installation Requirements

– For 1 phase supply, power must be connected to terminals L1/L and L2/N.

– For compliance with CE and C Tick EMC requirements, a symmetrical shielded motor cable is recommended.

– A fixed installation is required according to IEC 61800-5-1 with a suitable disconnecting device installed between the DC1 and the AC Power Source.

The disconnecting device must conform to the local safety code/regulations (e. g. within Europe, EN 60204-1, Safety of Machinery).

– The cables must be dimensioned according to the local codes or regulations. Motor Cable: 75 °C (167 °F) Copper must be used.

– Suitable fuses to provide wiring protection of the input power cable should be installed in the incoming supply to the data shown in this Instruction Leaflet.

– The fuses must comply with any local codes or regulations in place. In general, type gG (IEC 60269) or UL Class J fuses are suitable.

The max. Voltage rating for fuses is 600 V.

– Where allowed by local regulations, suitably dimensioned type B MCB circuit breakers of equivalent rating may be utilised in place of fuses, providing that the

clearing capacity is sufficient for the installation. The max. Voltage rating for MBCs is 480 V.

– When the power supply is removed from the drive, a minimum of 30 seconds should be allowed before re-applying the power.

A minimum of 5 minutes should be allowed before removing the terminal covers or connection.

– Transient surge suppression must be installed on the line side of this equipment and shall provide protection for a rated impulse withstand voltage peak of 4 kV.
Only a single conductor type is allowed in each field wiring terminal when connected in group installation arrangement.

Motor Overload Protection

DC1 provides motor overload protection in accordance with the National Electrical Code (US).

– Where a motor thermistor is not fitted, or not utilised, Thermal Overload Memory Retention must be enabled by setting P-51 = 0.

Set the parameters P1-08 “Current Limit” on motor current.

– Where a motor thermistor is fitted and connected to the drive, connection must be carried out according to the information, refer to Manual.

Terminal (ring lug)

Cable

Cable support

Cable

Cable

PE

Содержание DC1-S1 Series

Страница 1: ...jat ja opastusta saaneet henkil t saavat suorittaa seuraavat ty t Nebezpe razu elektrick m proudem N e uveden pr ce sm j prov d t pouze osoby s elektrotechnick m vzd l n m Eluohtlik Elektril gioht J r...

Страница 2: ...eut i Dimenzije i te ina FS a a1 b b1 b2 c c1 1 2 kg lbs FS1 DC1 S17D0 DC1 S24D3 DC1 S27D0 81 3 19 50 1 97 184 7 24 170 6 69 7 0 28 124 4 88 4 0 16 6 0 24 12 0 47 1 1 2 43 FS2 DC1 S1011 DC1 S2011 107...

Страница 3: ...t na kovovou desku Mont na kovov dosku Szerel s f mlemezre Mont a uz met la pl ksnes Montavimas ant metalin s plok t s Monta na metalowej p ytce Monta a na kovinsko plo o Mont na kovov dosku Montare p...

Страница 4: ...eed f REF t Boost s t dec s DC1 S Start Drive L1 L L2 N L3 U V W 1 2 3 4 5 6 7 8 9 10 11 1 2 3 4 5 6 7 8 9 10 11 DI1 Start DI2 DI3 f Fix1 24 V 100 mA 10 V 10 mA AI1 f REF 0 V AO f Out 30 V DC 5 A 0 V...

Страница 5: ...s i sp nningsfritt tillst nd POZOR Napravo priklju ite le ko ni pod napetostjo AVVISO Collegare solo in assenza di tensione ILMOITUS Kytke vain j nnitteett m ss tilassa UPOZORNRNIE Nap jat len v stave...

Страница 6: ...P A Fuse or MCB Type B gG J mm2 AWG kcmil A mm2 AWG kcmil kW HP RB res IEC UL1 DC1 S17D0 FS1 8 5 16 15 2 5 14 7 1 5 16 0 37 0 5 DC1 S1011 FS2 12 5 16 15 2 5 14 10 5 1 5 16 0 55 0 75 100 DC1 S24D3 FS1...

Страница 7: ...3 4 5 6 7 8 9 10 11 DI1 Start DI2 DI3 f Fix1 24 V 100 mA 10 V 10 mA AI1 f REF 0 V AO f Out 30 V DC 5 A 0 V RUN 4 7 k 0 10 V 20 mA DC1 S 250 V AC 6 A M3 mm2 mm2 AWG mm in Nm lb in mm 0 25 0 5 0 14 1 5...

Страница 8: ...Power L N PE U V DC DC RB b Control 1 2 n Modbus CANopen DC BR DC V U M 1 L1 L EMC L2 N VAR DC1 S1 1 AC 110 115 V DC1 S2 1 AC 200 240 V 50 60 Hz PES 2 DI1 Start 24 V 3 DI2 4 DI3 AI2 f Fix1 5 10 V Out...

Страница 9: ...ung Split phase motor Induktionsstartmotor Capacitor start induction motor Kondensatormotor mit Start Kondensator Switches at 75 of its rated speed Schaltet bei 75 der Nenndrehzahl Capacitor run induc...

Страница 10: ...n La plage de d marrage est param trer Debe parametrizarse el rea de inicio L area di avvio deve essere parametrizzata Het startgebied moet worden geparametreerd Startomr det skal parametreres A rea d...

Страница 11: ...above 2000 m is not UL approved Electrical Installation Requirements For 1 phase supply power must be connected to terminals L1 L and L2 N For compliance with CE and C Tick EMC requirements a symmetr...

Страница 12: ...kst s kt tikai tad ja ir konstat ta iek rtas atbilst ba Ma nu direkt v 2006 42 EK ietvertaj m aizsardz bas pras b m EMS atbilsto a uzb ve Vad bas un t kla kabe us izvietot atsevi i no motora kabe a p...

Отзывы: