3 Control signal terminals
3.2 Configuration of the control signal terminals
DC1…E1 Variable Frequency Drives
11/16 MN040022EN
www.eaton.com
25
3.2.10 P-12 = 9: SWD c setpoint value
Table 18: P-12 = 9: SWD c setpoint value
P-15
DI1
(terminal 2)
DI2
(terminal 3)
DI3/AI2
(terminal 4)
DI4/AI1
(terminal 6)
0
ENA
No function
No function
No function
1
Not permissible
2
Not permissible
3
Not permissible
4
Not permissible
5
Not permissible
6
Not permissible
7
Not permissible
8
Not permissible
9
Not permissible
10
Not permissible
11
Not permissible
12
Not permissible
13
ENA
No function
EXTFLT
No function
14
Not permissible
15
1)
ENA
No function
Select Fire Mode/Normal OP
No function
16
2)
ENA
Select AI1/f-Fix2
Select Fire Mode/Normal OP
AI1 REF
17
ENA
Select f-Fix Bit0
Select Fire Mode/Normal OP
Select f-Fix Bit1
1) If P-15 = 15 and fire mode is active, the drive will run with fixed frequency 4 (f-Fix4), which is set with P-13.
2) If P-15 = 16, the setpoint value selection will be independent from fire mode.