Eaton Cutler-Hammer Modbus mMINT Скачать руководство пользователя страница 8

Page 8

I.L. 66A7508H05

Effective September 2003

Register 3 high byte contains a value corresponding to
Engineering Units (power of 10 signed exponent). Register 3
low byte contains a Mantissa Multiplier value (power of 2
signed exponent).

Register 2 through registers 0 contains a 48-bit unsigned
energy mantissa in units of watthours.

The data format of these 4 registers is given in 

Figure 9

.

Energy = 2

Mantissa Multiplier

 x (48 bit unsigned energy value)

x  10

Engineering Units

.

Figure 9:  4-Register Energy Data Format

6.9  Supported Diagnostic Sub-Functions

It is possible to obtain diagnostics from the mMINT or an
attached INCOM product using function code 08. See 

Table 6

.

A single register is used for each UART counter within the
mMINT.  Each INCOM device and the mMINT contain a unique
slave counter.

To use mMINT address 247 or 248 in the diagnostic query
SW2-1 must be properly set. See Section 5.8 and 

Table 5

.

6.10 Exception Codes

Under certain circumstances, the mMINT will return an
exception code.

If the function in the query is not supported by the mMINT,
exception code 01 is returned in the response.

If the data (object) register is illegal, exception code 02 is
returned in the response.

If the data value in the query is illegal, exception code 03 is
returned.

If the slave INCOM product fails (usually a timeout), exception
code 04 is returned.

In certain circumstances, an exception code 05 (ACK) is
returned.

If the mMINT cannot perform the requested function, exception
code 07 (NAK) is returned.

If only a partial register is used in the query, exception code 84
is returned.

Sub-

function

No. #

(decimal)

Name

in the query use

0

echo query

mMINT or INCOM addr

1

restart communications

mMINT or INCOM addr

4

force listen

mMINT or INCOM addr

10

clear slave counters

mMINT or INCOM addr

11

UART bus message count

mMINT or INCOM addr

12

UART communication error count

mMINT or INCOM addr

13

slave exception error count

mMINT or INCOM addr

14

slave message count

mMINT or INCOM addr

15

slave no response count

mMINT or INCOM addr

16

slave NAK count

mMINT or INCOM addr

17

slave busy count

mMINT or INCOM addr

18

UART over run error count

mMINT or INCOM addr

20

clear UART counters

mMINT or INCOM addr

21

slave INCOM BCH error count

INCOM device addr

22

slave INCOM over run count

INCOM device addr

23

UART framing error count

mMINT or INCOM addr

24

UART noise error count

mMINT or INCOM addr

25

UART parity error count

mMINT or INCOM addr

26

mMINT firmware version & rev

mMINT addr

27

mMINT firmware month & day

mMINT addr

28

mMINT firmware year

mMINT addr

29

remove INCOM device(s)

mMINT or INCOM addr

30

reset INCOM routing addresses

mMINT addr

Table 6:  Diagnostic Sub Function Numbers

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Energy Register 0

Byte1 of Mantissa

Byte0 of Mantissa

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Energy Register 1

Byte3 of Mantissa

Byte2 of Mantissa

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Energy Register 2

Byte5 of Mantissa

Byte4 of Mantissa

15 14 13 12 11 10

9

8

7

6

5

4

3

2

1

0

Energy Register 3

Engineering Units

Mantissa Multiplier

Energy = 2

Mantissa Multiplier

 * Mantissa * 10

Engineering Units

Содержание Cutler-Hammer Modbus mMINT

Страница 1: ...ations 6 6 6 Command Data Pass Through 6 6 7 Control of INCOM Product 6 6 8 Energy Format 7 6 9 Supported Diagnostic Sub Functions 8 6 10 Exception Codes 8 7 0 Troubleshooting 9 APPENDIX A 9 Notes 19...

Страница 2: ...changes LED indicators for Modbus RS485 transmit and receive communications exchanges Input power for the module from either 120 Vac or 48 to 125 Vdc DIN rail mount package 0 C to 60 C ambient operati...

Страница 3: ...twork Make sure that there is twisted pair wire that is recommended for Modbus RTU network use Use shielded twisted pair wire to connect each slave to the Modbus RTU network daisy chain style The pola...

Страница 4: ...pproximately 1 second ON 1 second OFF However detection of a communications error on either the Modbus or INCOM network will result in an increased flashing rate approximately second ON second OFF The...

Страница 5: ...column of Table 7 or Table 8 can be established for each INCOM product attached to a mMINT Function code 16 1016 is used to load the object assignments for the block of registers The block assignments...

Страница 6: ...the configured sub network address accessed through a sub network master addressed at the INCOM main network address All INCOM Routing Address Configuration registers can be reset to their default st...

Страница 7: ...ter format is presented in units of Kwatthours and is valid for INCOM products reporting energy in watthours or Kwatthours only Products reporting in units greater than Kwatthours e g Mwatthours could...

Страница 8: ...ction exception code 07 NAK is returned If only a partial register is used in the query exception code 84 is returned Sub function No decimal Name in the query use 0 echo query mMINT or INCOM addr 1 r...

Страница 9: ...IN rail mounting 3 Control voltage is 120 VAC 20 or 48 125 VDC 4 Connectors are plug in types from Phoenix Contact 5 Terminal Types supplied with module are 3 point 4 point and 5 point Phoenix Contact...

Страница 10: ...N demand A 404649 406185 1228 1828 10 x real 3 ph power W 404651 406187 122A 182A 1 x x x x x x reactive 3 ph VAR 404653 406189 122C 182C 1 x x x x x x Power apparent 3 ph VA 404655 406191 122E 182E 1...

Страница 11: ...1892 1 x load bearing 1 o C 404757 406293 1294 1894 1 x load bearing 2 o C 404759 406295 1296 1896 1 x auxiliary o C 404761 406297 1298 1898 1 x Temperature device temperature o C 404763 406299 129A 1...

Страница 12: ...159 120E 180E 10 x x x x x x x x VBC V 404625 406161 1210 1810 10 x x x x x x x x VCA V 404627 406163 1212 1812 10 x x x x x x x x L L voltage VLLavg Vavg 404629 406165 1214 1814 10 x VAN V 404631 406...

Страница 13: ...nt B ph pf 404693 406229 1254 1854 100 x x apparent C ph pf 404695 406231 1256 1856 100 x x Power factor apparent pf 404659 406195 1232 1832 100 x x x x x x K factor K factor 404663 406199 1236 1836 1...

Страница 14: ...ed 13 Picked up 14 Phase A Trip 15 Phase B Trip 252 Product Specific Code 252 16 Phase C Trip 253 Product Specific Code 253 17 Neutral Trip 254 Product Specific Code 254 18 Ground Earth Trip 255 Produ...

Страница 15: ...lure 4 16 Over Frequency 55 Diagnostic failure 5 17 Current Unbalance 56 Diagnostic failure 6 18 Voltage Unbalance 57 Diagnostic failure 7 19 Apparent Power Factor 58 Diagnostic failure 8 20 Displacem...

Страница 16: ...ck 94 Load Bearing Temperature 136 Real Time Clock 95 Auxiliary Temperature 137 High Floating Voltage 96 Winding Temperature 138 Trip Blocked 97 Local Temperature 139 Incomplete Sequence 98 External T...

Страница 17: ...er 0 1 18 Reset min max current THD 0 1 19 Reset min max voltage THD 0 1 20 Reset min max per phase power 0 1 22 Reset op count runtime override count 0 1 36 Reset motor data maximum values 0 1 37 Res...

Страница 18: ...fer 5 0 4 Cancel ATS test 5 0 5 Go to emergency 5 0 6 Automatic Transfer Switch Control Cancel Go to emergency 5 0 7 Table 12 Control Slave Action Number Definitions continued Register10 Modbus Addres...

Страница 19: ...rchaser and Cutler Hammer Inc NO WARRANTIES EXPRESSED OR IMPLIED INCLUDING WARRANTIES OF FITNESS FOR A PARTICULAR PURPOSE OR MERCHANTABILITY OR WARRANTIES ARISING FROM THE COURSE OF DEALING OR USAGE O...

Страница 20: ...Page 20 I L 66A7508H05 Effective September 2003 Cutler Hammer Pittsburgh PA U S A Printed in U S A...

Отзывы: