I.L. 66A7508H05
Page 17
Effective September 2003
Control Group
Definition
Byte2
Byte1
Byte0
Reset alarm
0
0
1
Reset trip
0
0
2
Reset (peak) demand-watts
0
0
4
Reset energy (kilowatt hours)
0
0
8
Reset device software
0
0
16 (10
16
)
Reset time stamped event data buffers
0
0
32 (20
16
)
Reset (synchronize) demand watts window
0
0
64 (40
16
)
Snapshot command
0
0
128 (80
16
)
Reset (peak) demand-currents
0
1
1
Reset operations count (or trigger counters)
0
1
2
Reset run time
0
1
3
Reset all min/max values
0
1
4
Unlock waveform buffer (clear upload-in-progress)
0
1
5
Reset discrete input counters
0
1
6
Reset min/max currents
0
1
13
Reset min/max L-L voltages
0
1
14
Reset min/max L-N voltages
0
1
15
Reset min/max PF-apparent
0
1
16
Reset min/max PF-displacement
0
1
17
Reset min/max power
0
1
18
Reset min/max current THD
0
1
19
Reset min/max voltage THD
0
1
20
Reset min/max per-phase power
0
1
22
Reset op count, runtime & override count
0
1
36
Reset motor data maximum values
0
1
37
Reset motor trip & alarm counters
0
1
38
Reset locked-trigger # X (X = trigger number)
0
2
X
Reset source 1 available time
0
3
1
Reset source 1 connect time
0
3
2
Reset source 1 run time
0
3
3
Reset source 2 available time
0
3
4
Reset source 2 connect time
0
3
5
Reset source 2 run time
0
3
6
Reset load energized time
0
3
7
Reset transfer status
0
3
8
Reset
Reset tamper flag for sensor #X
0
4
X
Open request
1
0
0
Close request
1
0
1
Circuit Breaker
Open-Close
Trip request
1
0
2
No action
2
0
0
Start fast forward
2
0
1
Start fast reverse
2
0
2
Stop
2
0
3
Start
2
0
4
Start slow forward
2
0
5
Start slow reverse
2
0
6
Set direction to forward
2
0
7
Set direction to reverse
2
0
8
Motor
Start-Stop
Emergency override
2
0
10
Table 12: Control 'Slave Action Number' Definitions