Intelligent Technologies QCPort System Install Manual 

November 2005  

 

MN05001002E 

For more information visit 

www.eatonelectrical.com

  

Page 

10

 

QCPort Operating Modes 

Overview 

The QCPort system is capable of two operating modes: 

• 

Master-Slave 

• 

Peer 

When the system is intended to be used in a master-slave setting there is no 
configuration necessary other then setting the address (group ID) of each device to a 
unique address 

Peer devices require a configuration setting for normal operation.  Devices that will 
communicate peer are the S811 soft start and the user display (DIM).   

Understanding Master-Slave 

Master-Slave is when a single device (master) is responsible for scheduling all 
communication to the remainder of the devices (slaves).  In most cases, this will be 
limited to IO applications where a Network Adapter is controlling the IO and motor control 
devices.  A slave only communicates when it is communicated to; thus eliminating 
collisions.  Since there are no unscheduled communications in a Master-Slave system, 
the scan time of a QCPort system will be deterministic.   

An example of a Master-Slave system can be found in Figure 3: Example of Remote 
Connection Using QCPort. 

Understanding Peer 

Peer communication is when devices broadcast their messages on event transitions or a 
time base to a specific device or groups of devices.  Unlike Master-Slave, this mode has 
no master scheduler in the system, and all devices produce data on an internal schedule 
or when an event occurs (e.g., input transition, fault).  In this mode, there is collision 
detection to detect if a message is damaged by two devices talking at the same time.  If 
this occurs, then the devices both stand off (at different stand off times) for a period of 
time and attempt to re-transmit the message. 

An example of a Peer-to-Peer system can be found in Figure 2: Example of Multiple 
Peripherals on One Device Using QCPort. 

Содержание Cutler Hammer MN05001002E

Страница 1: ...MN05001002E C For more information visit www eatonelectrical com Intelligent Technologies QCPort System Install Manual November 2005 Supercedes November 2004...

Страница 2: ...f this control equipment must satisfy themselves that all necessary steps have been taken to assure that each application and use meets all performance and safety requirements including any applicable...

Страница 3: ...of the product National Electric Code Warning Do not install or perform maintenance on the QCPort system while the system is energized Death or severe personal injury as well as damage to other equipm...

Страница 4: ...A QCPORT SYSTEM 11 QCPort Backplane 11 QCPort Interconnect Cable 12 DAISY CHAIN 14 TRUNK DROP 14 PHYSICAL PLACEMENT 15 USING BIASING RESISTORS 16 APPLICATION EXAMPLE 17 PLANNING A QCPORT INTERCONNECT...

Страница 5: ...3 Example of Remote Connection Using QCPort 9 Figure 4 QCPort Backplane Connector 11 Figure 5 6 Pin QCPort Linear Connector 11 Figure 6 QCPort Interconnect Cable 12 Figure 7 QCPort Powered Interconne...

Страница 6: ...intelligent device into a single device port for the means of control setup and configuration The integration of these capabilities provides interface options that are powerful and cost effective In a...

Страница 7: ...er interface and operator stations Figure 1 Example of One Device Using QCPort The interconnect supplied with the operator interface connects the operator interface to the motor controller This connec...

Страница 8: ...modules The input module is used to apply a hard wired HOA while the output module is used to annunciate the motor controller status and trip conditions The mapping of the data between the motor contr...

Страница 9: ...required refer to Locating a Power Supply later in this manual Along with the power supply sizing physical media restrictions must be followed This includes the length of the interconnects type of in...

Страница 10: ...tor control devices A slave only communicates when it is communicated to thus eliminating collisions Since there are no unscheduled communications in a Master Slave system the scan time of a QCPort sy...

Страница 11: ...feet 300 meters 230Kbaud In this case special care has to be taken to size the power supply correctly for the distance QCPort Backplane The QCPort backplane provides a convenient way to connect the Ne...

Страница 12: ...rt Interconnect cable is ordered from the factory at preconfigured standard lengths QCPort devices provide two QCPort interconnect cable plug connections that are in parallel so that the devices can b...

Страница 13: ...ong Run Cable Connection Long Run Cable Recommended Manufacturers Table 1 Manufacturers and Part Numbers for Long Run Cables Manufacturer Part Number Belden 82842 Plenum Rated Belden 9842 Non Plenum R...

Страница 14: ...han 10 feet 3 meters are required between devices there are other methods that include using a long run cable and connectors Methods of connection include using QCPort Interconnect Cable QCPort Backpl...

Страница 15: ...rt Backplane Long Run or any combination of the three Physical Placement When planning the connection care should be taken as to the physically placement of the devices Considerations include Grouping...

Страница 16: ...hest from the network Adapter A biasing resistor is not required on the one end that the Network Adapter is located since the Network Adapter has a biasing resistor integral When a biasing resistor is...

Страница 17: ...and the change from the backplane to the QCPort Interconnect cable is performed there as well When powering the QCPort system the power supply that provides power to the starters is the same power su...

Страница 18: ...to NEC and CE Code limits respectively Use a power supply that has its own current limit protection Make sure you derate the supply for temperature using the manufacturer s guidelines Provide fuse pr...

Страница 19: ...t be between 18 and 28V DC Locating a Power Supply The QCPort interconnect system allows several options for supplying power as outlined in this section To determine which option meets your needs cons...

Страница 20: ...e location Warning If you use more than one power supply all of them should be attached to the same earth ground Ground the G conductor at only one place at the power supply that is closest to the phy...

Страница 21: ...wer supply for the expected temperature using the manufacturer s guidelines Use a power supply that has its own current limit protection Adjusting the Configuration When the sections have a voltage dr...

Страница 22: ...drop allowed This is the total cable system voltage drop of 5 00V minus 0 35V reserved for drop line voltage drop Nt The number of taps between the device being evaluated and the power supply For exam...

Страница 23: ...have to be relocated Example 2 End Connected Power Supply 1 Sum up the currents QCPort Interconnect system 0 1 0 4 0 3 0 8 A OK since 10 feet allows 1 0A 2 Find the voltages for each node using the e...

Страница 24: ...0 105 Nt x 0 005 x In 4 65V Device 1 9 x 0 105 3 x 0 005 x 0 2 0 19V Device 2 6 x 0 105 2 x 0 005 x 0 3 0 19V Device 3 3 x 0 105 1 x 0 005 x 0 1 0 03V Device 4 0 x 0 105 1 x 0 005 x 1 0 0 00V Device 5...

Страница 25: ...QCPort System Install Manual November 2005 MN05001002E For more information visit www eatonelectrical com Page 25 Troubleshooting and Maintenance Refer to the selected device manuals for more detailed...

Страница 26: ...QPLR provides for screw lugs for connection to industrial RS485 cable Example of Long Run Cable One Power Supply End Connected The following example uses the full calculation method to determine the...

Страница 27: ...Run SUM L n x 0 0045 N t x 0 005 x I n 4 65V Device 1 18 x 0 021 1 x 0 005 x 1 0 0 383V Device 2 36 x 0 021 2 x 0 005 x 0 5 0 383V Device 3 43 x 0 021 3 x 0 005 x 0 4 0 367V Device 4 95 x 0 021 4 x 0...

Страница 28: ...001002E For more information visit www eatonelectrical com Page 28 Technical Support For additional information on this product Please call our Customer Support Center at 1 800 356 1243 For service or...

Страница 29: ...eds of the industrial utility light commercial residential and OEM markets For more information visit www eatonelectrical com Eaton Corporation is a global diversified industrial manufacturer with 200...

Отзывы: