![Eaton Cutler-Hammer ATC-300 Скачать руководство пользователя страница 8](http://html1.mh-extra.com/html/eaton/cutler-hammer-atc-300/cutler-hammer-atc-300_operation-and-maintenance-manual_3839423008.webp)
For more information visit: www.eaton.com
IB140042EN
Instructional Booklet
Page
8
Effective: May 2015
ATC-300/ 900 Breaker Based Transfer Switch
Figure 7. Typical Power Panel for 225-1200 A Models.
Figure 8. Typical Power Panel for 30-150 A Models.
3.2.1 Steel Base Plate
The steel base plate design (225-1200 A models only) permits the
power panel to be moved vertically within the enclosure to accom-
modate top or bottom cable entry. Elongated holes on either side
of the base plate ensure proper positioning. The bottom set of
elongated holes positions the power panel higher in the enclosure,
thus permitting bottom cable entry. The top set of elongated
holes positions the power panel lower in the enclosure for top
cable entry. Section 4 discusses equipment mounting and load
lug location in detail.
3.2.2 Main Contacts
This ATS incorporates Eaton-type molded case switches. The
main contacts connect and disconnect the load to and from the
different power sources. High-withstand molded case switches
are the main contacts for the Source 1 and Source 2 power
sources in standard switch ATSs (Figure 9
and Section 3.7).
These continuous duty transfer switches are rated for all classes
of loads, open or enclosed.
Figure 9. Mounted Molded Case Switches with the Transfer
Mechanism Removed for Clarity (225-1200 A Models).
In addition, they have high dielectric strength, heavy-duty switch-
ing, high-withstand capabilities, and high interruption capacity.
The switching devices are mechanically and electrically inter-
locked to prevent the two sets of main contacts from being closed
simultaneously. The load side contacts of each switching device
are joined with a bus bar assembly to form a common load termi-
nal location, either top or bottom (Figures 10 and 11).