![Eaton Cutler-Hammer ATC-300 Скачать руководство пользователя страница 26](http://html1.mh-extra.com/html/eaton/cutler-hammer-atc-300/cutler-hammer-atc-300_operation-and-maintenance-manual_3839423026.webp)
For more information visit: www.eaton.com
IB140042EN
Instructional Booklet
Page
26
Effective: May 2015
ATC-300 /900 Breaker Based Transfer Switch
4.8 Voltage Selection Adjustments
Certain devices, such as the Voltage Selection Panel, sensing
relays, and timers, need to be set and/or calibrated prior to placing
the ATS equipment in service. Adjustments for controller are
described in the separate instructional document dedicated to the
specific controller being used. Voltage selection adjustments are
described in this section.
BE SURE THAT THE CORRECT VOLTAGE IS SELECTED TO MATCH
THE SYSTEM VOLTAGE. AN IMPROPER SELECTION AND/OR CON-
NECTION COULD RESULT IN EQUIPMENT DAMAGE.
4.8.1 North American Market
Voltage Selection
Panels (120,
208, 240, 480, and 600 V, - 60 Hz)
Vertical and Horizontal Design Voltage Selection
The North American market Voltage Selection Panel consists of
multi-tap transformers, contained in a steel case mounted in the
enclosure. The cover has “teardrop” holes for the screws to allow
easy access to the transformers. To change the voltage from the
factory default 600 Vac, follow the steps detailed below.
Step1:
Loosen the four screws securing the cover of the Voltage
Selection Transformer case. Slide the cover up, then
away from the case.
Step 2:
Remove the wires from the primary taps of both trans-
formers and installed them on the taps for the desired
voltage (Figure 25). Note that only one wire per trans-
former is moved since the second wire is the zero refer-
ence.
WHEN CHANGING THE VOLTAGE, ONE WIRE MUST BE MOVED ON
THE PRIMARY TAPS OF BOTH TRANSFORMERS.
Figure 25. North American Market Voltage Selection Panel with
Voltage Being Selected.
Step 3:
Reinstall the cover and tighten the four screws.
4.8.2 International Market Power Panels (208, 220, 240,
380, 415, and 600 V - 50-60 Hz)
Vertical Design Voltage Selection
The vertical design transfer switch is furnished with a multi-tap
Voltage Selection Panel to the right of the power panel. Seven
front accessible taps from 208 to 600 Vac are provided (Figure
26). A small disconnect plug is provided to change from one volt-
age to another. The transfer switch is shipped with the plug in
the 600 Vac position.
Horizontal Design Voltage Selection
Horizontal design transfer switches are furnished with an adjust-
able line voltage plug and receptacles below the power panel. To
change the line voltage, insert the plug in the desired receptacle
(Figure 26). The transfer switch is shipped with the plug in the
600 Vac position.
CAUTION
CAUTION