![Eaton Cutler-Hammer ATC-300 Скачать руководство пользователя страница 39](http://html1.mh-extra.com/html/eaton/cutler-hammer-atc-300/cutler-hammer-atc-300_operation-and-maintenance-manual_3839423039.webp)
IB140042EN
For more information visit: www.eaton.com
Instructional Booklet
Effective: May 2015
Page
39
ATC-300/900 Breaker Based Transfer Switch
Figure 42. Dual Utility Transfer Switch
Dual Utility Transfer Switch
Source 1 is available
Close Source 1
(Energize K1)
Source 1 is powering the load
Source 1 becomes unavailable
(or Go To Emergency)
Is Source 2
Available?
TDNE timer times out
Open Source 1
(Energize K2)
Close Source 2
(Energize K4)
Source 2 is powering the load
Is Source 1
Available?
TDEN timer times out
Yes
No
No
Yes
Open Source 2
(Energize K1)
Close Source 1
(Energize K3)
Source 1 is powering the load
Sends pretransfer signal
TPRE timer times out
(If Source 1 is Available)
Sends pretransfer signal
TPRE timer times out