manualshive.com logo in svg
background image

Quick Install Guide

The below steps can be followed to quickly install a CurrentWatch 

EDC Series sensor.

1.  Run the wire to be monitored through the aperture, being sure 

monitored current flow matches arrows on the sensor or as 

noted on the figure to the right on this page.

2.  Mount the sensor to a surface, if needed.
3.  Connect output wiring:

a.  Use up to 14 AWG (2.5 mm

2

) copper wires, tightening termi-

nals to 5.3 in.-lbs / 0.60 N·m of torque.

b.  For current output models, make sure output load is no more 

than 500 ohms.

4.  Connect power using the appropriate power supply.
5.  Select the correct range by positioning the Range Jumper.

Installation 

Considerations for all EDC Series models…

• 

Run wire to be monitored through the aperture (opening) of the 

sensor.

• 

Care should be taken to ensure current flow is in accordance with 

any directional arrows on the sensor and as noted in the figure on 

the right of this page.

• 

These sensors can be located in the same environment as 

motors, contactors, heaters, pull-boxes, and other electrical enclo-

sures.

• 

Mounting can be done in any position or hung directly on a wire 

with a wire tie.

• 

For optimal performance, ensure the unit has been energized for a 

period of 20 minutes prior to sensing operation.

Range Selection

The CurrentWatch EDC Series sensors feature field selectable rang-

es.  The ranges are factory calibrated, eliminating time consuming 

and inaccurate field setting of zero or span. 

Stooing Rangt

1.  Determine the normal operating amperage of your monitored 

current.

2.  Select the range this is equal to or slightly higher than the nor-

mal operating amperage.

3.  Place the Range Jumper in the appropriate position.

Wiring and Mounting Information

Connect control or monitoring wires to the sensor.  Use up to 14 

AWG copper wire and tighten terminals to 5.3 in.-lbs / 0.60 N·m 

maximum torque. 

3 .3 7 5  in.

(8 5 .7 3 m m

EDC1420SC

DC Current Sensor

MID

HIGH

JUM PER  RA NGE

M ID

1 0 A

HIGH

2 0 A

POWER

+

-

4-20mA

Output

1

2

3

4

Current Direction

U

n

ipo
la

r

B

ipo
la

r

(+)

(-)

CNnntcoiNn NNotse:

• 

The current loop is powered by the sensor.  Maximum loop 

impedance is 800 ohms.

• 

Ensure the direction of the monitored current is the same as the 

direction shown on the diagram. The unipolar output design will 

not operate properly if the current is opposite the direction of the 

arrow.

• 

Use 26-14 AWG copper wire.

• 

Screw thread is M3 and screw torque is 5.3 in.-lbs / 0.60 N·m.

• 

Remove jumper entirely for Low Range operation.

• 

Observe polarity.

Unipolar Versus Bipolar Output

Output

Diagram

Unipolar Output

Bipolar Output

4

2 0

O

u

tpu

t 

(m

A

)

F S

0

R a n g e

(S e n se d  C u rre n t,  A )

F S

- F S

R a n g e (S e n se d  C u rre n t,  A )

4

2 0

1 2

O

u

tpu

t       

 (

m

A

)

)

2

EATON 

www.eaton.com

CurrentWatch™ EDC Series Current Sensors, 

DC Current Sensor, Solid Core Housing with 

Analog Output

Instructions Publication 

P51926

Effective July 2017

Содержание CurrentWatch EDC Series

Страница 1: ...сты или проинструктированные лица могут выполнять следующие операции Levensgevaar door elektrische stroom Uitsluitend deskundigen in elektriciteit en elektrotechnisch geïnstrueerde personen is het toegestaan de navolgend beschreven werkzaamheden uit te voeren Livsfare på grund af elektrisk strøm Kun uddannede el installatører og personer der e instruerede i elektrotekniske arbejdsopgaver må udføre...

Страница 2: ...re field selectable rang es The ranges are factory calibrated eliminating time consuming and inaccurate field setting of zero or span Setting Range 1 Determine the normal operating amperage of your monitored current 2 Select the range this is equal to or slightly higher than the nor mal operating amperage 3 Place the Range Jumper in the appropriate position Wiring and Mounting Information Connect ...

Страница 3: ...current being sensed Change the jumper position Specifications Specification Value Power Supply 24 VAC DC 22 28 VAC DC Power input and output signal are not isolated Caution Do not connect Grounded AC Supply to the Output Negative as sensor damage may occur Power Consumption 2 VA Current Ranges Jumper Selectable 5 10 or 20 A Output Signal 4 20 mA Response Time 160 ms 90 of Step Change Repeatabilit...

Страница 4: ...ensors 2017 by Eaton All Rights Reserved Printed in USA Publication No P51926 003 July 2017 CurrentWatch EDC Series Current Sensors DC Current Sensor Solid Core Housing with Analog Output Instructions Publication P51926 Effective July 2017 Eaton Industries GmbH Hein Moeller Straße 7 11 53115 Bonn Germany Eaton W126 N7250 Flint Drive Menomonee Falls WI 53051 USA Eaton Electrical Sector Sensors 1 80...