EATON’s Crouse-Hinds Business

GB

Explosion-protected plugs and sockets 125 A, GHG 515

6.3.2  Plug

In general, only the sealing inserts, Fig. 6, Item 
12, fitted in the plug may be used. 

When mounting the cable, ensure that the 
sealing inserts match the cable diameter used. 

After connecting the cable, screw down the cap 
nut , Fig. 6, Item 4, by hand until it seals. Then 
tighten down the screws, Fig. 6, Item 5,  of the 
pull-relief, Fig. 6, Item 6.

Warning! Overtightening might impair the 
pull-relief or damage the connection cable.

6.4  Closing the device

In order to ensure the required minimum 
protection category, the cover screws and the 
screws of the plug  shall be tightened down.

Any foreign matter shall be removed from 
the device overtightening might impair the 
protection category.

6.5  Taking into operation

Prior to taking the apparatus into operation, the 
tests specified in the relevant national 
regulations shall be carried out. In addition to 
this, the correct functioning and installation of 
the apparatus in accordance with these 
operating instructions and other applicable regu-
lations shall be checked.  

Check the plug for any damage before 
inserting it in the socket.

The user shall ensure that as equipotential earth 
applies throughout when the plug and socket 
system is in operation.

The improper installation and operation of 
the plugs and sockets may result in the 
invalidation of the guarantee. 

Maintenance / Servicing

The valid national regulations for the 
servicing / maintenance of electrical 
apparatus for use in potentially explosive 
atmospheres shall be observed  
(IEC/EN 60079-17).

Prior to opening the enclosure, it is 
necessary to ensure that the voltage supply 
has been isolated or to take suitable 
protective measures.

The necessary intervals between servicing 
depend upon the specific application and shall 
be stipulated by the operator according to the 
respective operating conditions.

During servicing, above all, the parts on which 
the explosion protection depends, (e.g. 
intactness of the flameproof components, the 
enclosure, the seals and cable entries), shall be 
checked.

If, in the course of servicing, it is ascertained, 
that repairs are necessary, Section 8 of these 
operating instructions shall be observed.

 Repairs / Modifications

Only original COOPER CROUSE-HINDS parts 
shall be used for carrying out repairs.

In the event of damage to the flameproof 
encapsulation,  replacement of these 
components is mandatory.

In case of doubt, the respective apparatus 
shall to be returned to COOPER CROUSE-
HINDS for repair.

Repairs that affect the explosion protection. 
May only be carried out by COOPER 
CROUSE-HINDS or a qualified electrician in 
compliance with the applicable national 
regulations (EN 60079-19).

Modifications or changes to the device are 
not permitted.  

9 Disposal/Recycling

The respective valid national regulations for 
waste disposal shall be observed when 
disposing of apparatus.

To facilitate the recycling of individual parts, 
parts made of moulded plastic shall bear the 
marking for the type of plastic used.

The product range is subject to changes and 
additions.

  

  

      2 

 

11

            3

 

 

12 

   6

    5

 

 

 

       4

    3

  2

  5 

 

 

 

     5

   L2 

 

 

 

   L3

   L1 

 

 

 

    N

    3

    PE

  2 

 

 

 

     11

Fig. 3

Fig. 4

Fig. 5

Fig. 6

Содержание Crouse-Hinds GHG 515

Страница 1: ...ig GHG 515 Explosion protected plugs and sockets 125 A 4 pole and 5 pole GHG 515 Fiche et prise de 125 A à 4 pôles et 5 pôles pour atmosphères explosives GHG 515 GHG 510 7004 P0001 D E F f Betriebsanleitung Operating instructions Mode d emploi CEAG Products ...

Страница 2: ...tions 8 3 Conformity with standards 8 4 Field of application 8 5 Application Properties 8 9 6 Installation 9 6 1 Mounting 9 6 2 Opening the device Electrical connection 9 6 3 Cable entry KLE blanking plug 9 10 6 3 1 Sockets 9 6 3 2 Plug Coupler 10 6 4 Closing the device 10 6 5 Putting into operation 10 7 Maintenance Servicing 10 8 Repairs Modifications 10 9 Disposal Recycling 10 Declaration of con...

Страница 3: ...3 0 Einschraubgewinde der KLE M63 7 5 Nm 1 Der max Klemmbereiche für Leitungen mit der Kombination aus Dichtung 1 2 kann je nach verwendetem Leitungstyp und Anwendung variieren 2 Bei derWahl der Dichtungsgummis ist darauf zu achten dass bei zukünftigenWartungsarbeiten an der KLE die Druckschraube nachgezogen werden kann Stecker Ø 21 48 mm Ø 31 58 mm Anschlussklemme Wandsteckdose Stecker 2 x 4 70 m...

Страница 4: ...er Crouse Hinds Niederlassung erfragen 5 Verwendung Eigenschaften Die Steckvorrichtungen GHG 515 dienen zur Stromversorgung von standortvariablen Vor Ort Steuerungen elektrischen Anlagen sowie von beweglichen Maschinen und Antrieben in explosionsgefährdeten Bereichen Die Steckvorrichtungen sind auch im normalen Industriebereich verwendbar Die Steckvorrichtungen für Niederspannungen GHG 515 sind mi...

Страница 5: ...ressen der Kabelschuhe auf das Kabel ist fachgemäß durchzuführen Es ist sicherzustellen dass die erforderlichen Mindestluftstrecken eingehalten werden bei 690V 12 mm 7 9 8 3 2 6 4 5 7 9 7 9 6 3 Kabel und Leitungseinführungen KLE Verschlussstopfen 6 3 1 Steckdosen Es dürfen generell nur bescheinigte KLE und Verschlussstopfen verwendet werden Für bewegliche Leitungen sind Trompeten verschraubungen o...

Страница 6: ...ah men ergreifen Die erforderlichenWartungsintervalle sind anwendungsspezifisch und daher in Abhängig keit von den Einsatzbedingungen vom Betreiber festzulegen Im Rahmen derWartung sind vor allem dieTeile von denen die Zündschutzart abhängt zu prüfen z B Unversehrtheit der druckfesten Komponenten des Gehäuses der Dichtungen und der Kabel und Leitungseinführung Sollte bei einerWartung festgestellt ...

Страница 7: ...her IP 66 catalogue version Insulation class acc to EN IEC 61140 I is complied with by devices Cab le entry standard version Wall socket 2 x M63 Ø 29 41 mm suitable cables and test torques of the pressure srew Ø Nm seel 1 2 1 2 min max 1 2 29 0 35 0 12 0 12 0 seel 2 1 2 min max 2 36 0 41 0 12 0 13 0 Test torque for screw in thread cable entry 7 5 Nm 1 The maximum clamping area for cables with the ...

Страница 8: ... enclosure materials employed including the exterior metal parts are made of high quali ty materials which ensure a corrosion protec tion and resistance to chemical substances corresponding to the requirements in a normal industrial atmosphere impact resistant polyamide glass fibre reinforced polyester special steel AISI 316 L In case of use in an extremely aggressive atmosphere please refer to ma...

Страница 9: ...tions as well as the required minimum cross section for the current load shall be observed see technical data All screws and or nuts of the supply terminals including the unused ones shall be tightened down The supply terminals are designed for the connection of copper conductors If multi or fine wire connecting cables are used the wire ends will have to be handled in acc with the applicable natio...

Страница 10: ...intenance of electrical apparatus for use in potentially explosive atmospheres shall be observed IEC EN 60079 17 Prior to opening the enclosure it is necessary to ensure that the voltage supply has been isolated or to take suitable protective measures The necessary intervals between servicing depend upon the specific application and shall be stipulated by the operator according to the respective o...

Страница 11: ... 1 Lorsque les bagues 1 2 sont utilisées la capacité de serrage maximale peut varier légèrement selon le type de câble utilisé 2 Lors de la sélection des bagues d étanchéité au moment de l installation il faut s assurer qu il reste une marge de serrage suffisante au niveau du chapeau du presse étoupe Cela permettra de pouvoir resserrer le presse étoupe lors d une future maintenance Fiche Ø 21 48mm...

Страница 12: ...tre la corrosion et une résistance contre des agents chimiques en atmosphère industrielle normale polyamide résistant au choc polyester renforcé par fibre de verre acier spécial AISI 316 En cas d utilisation en atmosphère extrème ment corrosive vous pouvez obtenir des informations complémentaires sur la résistance chimique des plastiques utilisés chez la succursale Cooper Crouse Hinds de votre rég...

Страница 13: ...eurs ainsi que les sections minimales requises pour la charge de courant doivent être respectées voir caractéristiques techniques Toutes les vis et ou écrous des bornes de connexion aussi celles des bornes non utilisées doivent être serrées à fond Afin de maintenir le mode de protection contre l explosion le raccordement des conducteurs doit se faire très soigneuse ment Attention Les cosses de câb...

Страница 14: ...ien du matériel électrique pour atmosphère explosive devra être respectée CEI EN 60079 17 Avant d ouvrir l enveloppe débrancher le dispositif de la tension ou prendre des mesures préventives appropriées Les intervalles de service requis dépendent de l emploi spécifique et devront donc être fixés par l utilisateur en tenant compte des condi tions d exploitation Lors de l entretien des appareils sur...

Страница 15: ...15 EATON s Crouse Hinds Business Notizen Notes Remarques ...

Страница 16: ...de la Union Europea EST Seda kasutusjuhendit oma riigikeeles võite küsida oma riigis asuvast asjaomasest Cooper Crouse Hindsi CEAG esindusest FIN Tarvittaessa tämän käyttöohjeen käännös on saatavissa toisella EU n kielellä Teidän Cooper Crouse Hinds CEAG edustajaltanne GR Cooper Crouse Hinds CEAG H A kezelési útmutatót az adott ország nyelvén a Cooper Crouse Hinds CEAG cég helyi képviseletén igény...

Страница 17: ...se aluminium wiring Use copper wire only To avoid electrical shock electrical power must be off before and during installation inspection and maintenance To avoid electrical shock always disconnect primary power source before opening device or enclosure for inspection or service Observe the national safety rules and regulations Explosion protected plug and socket system 100 A 4 pole and 5 pole GHG...

Страница 18: ...lied with by the devices Cable entry catalogue version Wall socket 2 x M50 1 x hub M50 1 2 NPT 1 x blanking plug plug Ø 21 48 mm Ø 31 58 mm Supply terminal Wall socket 2 x AWG 11 00 max 1xAWG 0000 Plug 1 x AWG 11 2 with pin cable lugs 1xAWG1 use cable lugs supplied Observe current load Min cross section Supply terminal Wall socket Plug for 100A rated current 1x 50 mm 1x AWG 2 for 125A rated curren...

Страница 19: ...rom the inside of the plugs and sockets Observe the national safety rules and regulations for prevention of accidents as well as the safety instructions included in these operating instructions and set in italics the same as this text Annex to operating instructions Plug and socket system 100A GHG 515 4 Field of application The plugs and sockets GHG 515 are suitable for use in Class I Zone 1 Class...

Страница 20: ... terminal Annex to operating instructions Plug and socket system 100 A GHG 515 7HQWR QiYRG N SRXåLWt VL P åHWH Y åiGDW YH VYpP PDWHĜVNpP MD FH X SĜtVOXãQpKR DVWRXSHQt VSROHþQRVWL RRSHU URXVH LQGV YH YDãt HPL 0RQWDJHYHMOHGQLQJHQ NDQ RYHUV WWHV WLO DQGUH 8 VSURJ RJ UHNYLUHUHV KRV HUHV RRSHU URXVH LQGV OHYHUDQG U Q FDVR QHFHVDULR SRGUi VROLFLWDU GH VX UHSUHVHQWDQWH RRSHU URXVH LQGV HVWDV LQVWUXFFLRQH...

Отзывы: