Table 10 . Function codes (continued)
Parameter
Unit of
Measure
Security Level
Default Value
Key Entry Limit
To Read
To Write
To Reset
Low
High
521 Present Voltage
Reduction Step
XX
---
View
NA
NA
NA
NA
NA
•The Remote Pulse Voltage Reduction Present Voltage Reduction Step for Alternate
Configuration 2.
522 SOFT-ADD-AMP
Limits
Off
---
View
Modify
NA
Off
NA
NA
•The SOFT-ADD-AMP Limits feature enabled for Alternate Configuration 2.
523 SOFT-ADD-AMP
High Limit
XX
---
View
Modify
NA
16
NA
NA
•The SOFT-ADD-AMP High Limit for Alternate Configuration 2.
524 SOFT-ADD-AMP
Low Limit
XX
---
View
Modify
NA
-16
NA
NA
•The SOFT-ADD-AMP Low Limit for Alternate Configuration 2.
525 Voltage Limiter
Mode
Off
---
View
Modify
NA
Off
NA
NA
•Voltage Limiter Mode enabled for Alternate Configuration 2.
526 High Voltage
Limit
XXX.X Volts
Volts
View
Modify
NA
130.0
120.0
135.0
•The Voltage Limiter High Limit for Alternate Configuration 2.
527 Low Voltage
Limit
XXX.X Volts
Volts
View
Modify
NA
105.0
105.0
120.0
•The Voltage Limiter Low Limit for Alternate Configuration 2.
528 Voltage Limiter
Fast Resp. Delay
XX Seconds
Seconds
View
Modify
NA
3
1
60
•The Voltage Limiter Fast Resp. Delay for Alternate Configuration 2.
529 Voltage Limiter
Delay
XX Seconds
Seconds
View
Modify
NA
10
1
60
•The Voltage Limiter Delay for Alternate Configuration 2.
530 Time Between
Taps
XX Seconds
Seconds
View
Modify
NA
0
0
10
•The Voltage Limiter Time Between Taps for Alternate Configuration 2.
531 Tap To Neutral
Off
---
View
Modify
NA
Off
NA
NA
•The Tap to Neutral setting for Alternate Configuration 2.
532 Bias Co-Gen Alt
Mode
Locked Reverse
---
View
Modify
NA
Locked
Reverse
NA
NA
•The Bias Co-generation Alt Mode setting for Alternate Configuration 2. See FC 58.
91
INSTALLATION, OPERATION, AND MAINTENANCE INSTRUCTIONS
MN225003EN April 2018